For full functionality of this site it is necessary to enable JavaScript.

Ainuo AN9640A(F) Electrical Safety Comprehensive tester (5000V/100mA, start test)

1) AC Hipot test
Booster rated output capacity: 500VA(5000V/100mA)
Booster maximum short-circuit current: >200mA 
Output waveform: Sine wave
Frequency setting: 50Hz/60Hz
Current upper-limit: 0.10~99.99mA
Current lower-limit:  0.00~10.00mA 
Time setting:  1~999s 
2)Insulation Resistance test
Rated output capacity: 2VA(1000V/2mA)
Output voltage setting: DC 500V or 1000V
Resistance upper-limit range: 0.0~99.9 MΩ,100~2000MΩ
Resistance lower-limit range: 0.3~99.9 MΩ, 100~2000MΩ 
Insulation resistance measurement:  0.0~99.9 MΩ, 100~2000 MΩ 
3) Ground Bond Resistance test
Output current setting: 3~30A 
Current frequency setting: Sine waveform 50Hz/60Hz
Dimension: 426(W)x 178(H)x 600(D)
Gross weight: 50 kg

Details

 

Product Detail

Main features
* Fullfill Latest international standard:500VA AC Hipot capacity(AC 5KV/100mA),short-circuit output current up to 200mA,Built-in optional leakage current test network MD card,meeting requirements of different industrial standards,Maximum test current of ground bond is up to 64A,optionalground bond resistance or voltagte test mode. Comply with CCC,IEC,EN,VDE,BS,UL,JIS standard requirements.
*Up to 6 functions:AC Hipot,insulation resistance,Ground Bond,leakage current,runing power,low-voltage start,flexibly configured for different models.
* Intelligent operation:15 groups of test memories,7-step programming for each guoup,button start.External programmable power supply,auto-comfiguration of power voltage/frequency for the DUT(Device under test).
*Auto control:standard RS232,Optional RS485/GPIB/LAN interface,AN97 power supply interface,Remote interface,easily compose automation system.
* Infomation management:optional software(ESRS),realizing test process and data management,improving product quality and production management level.
*Simplified operation:LED backlit screen display,menu operation,Chinese/English,socket test fixture.
Order information and extended functions
* AN694A(F):6 in 1,external AN97 series power supply is required for leakage/power/start test,Safety capacity 500VA
*AN9640B(F):5 in 1,external AN97 series power supply is required for leakage,power test.
eakage/power/start test,Safety capacity 500VA
*AN9640B(F):5 in 1,external AN97 series power supply is required for leakage,power test.

Spec.

<t

AC Hipot test

 

Booster rated output capacity

AN9640A(F)

500VA5000V/100mA)1

 

AN9640B(F)

100VA5000V/20mA

 

Booster maximum short-circuit current

>200mA

 

Output waveform

Sine wave, <3%pure resistance5000V/1mA),<3%From empty load to full load

 

distortion and regulation

 

Output voltage setting

Range

5005000V

 

Resolution

5V

 

Accuracy

±3%×setting+10V

 

Frequency setting

Range

50Hz/60Hz

 

Accuracy

±0.1%×setting

 

Alarming limits setting

Current upper-limit

0.1099.99mA(20.00mA for AN9640B/C(F))

 

Current lower-limit

0.0010.00mA

 

Compensation current setting

Range

0.0010.00mA, automatic testing, compensation can be set to ON/OFF

 

Time setting

Range

1999s

 

Ramp up time range

1100s

 

Accuracy

±0.1%×setting+1count

 

Breakdown current alarm

Range

0.1099.99mA(20.00mA for AN9640B/C(F))

 

Accuracy

±3%×reading+3counts

 

Insulation Resistance test

 

Rated output capacity

2VA1000V/2mA

 

Output voltage regulation

<3%From no load to full load

 

Output voltage ripple

<1%

 

Output voltage setting

Range

DC 500Vor1000V

 

Accuracy

±3%×setting+3counts

 

Alarming limits setting

Resistance upper-limit range

0.099.9 MΩ1002000MΩIf upper-limit is set to 0, it will not make adjudgment for upper limit

 

Resistance lower-limit range

0.399.9 MΩ, 1002000MΩ

 

Time setting

Range

1999s

 

Accuracy

±0.1%×setting+1count

 

Insulation resistance measurement

Range

0.099.9 MΩ, 1002000 MΩ

 

Accuracy

≤200MΩ: ±3%×reading+3counts

 
 

RemarksExcept 500V and 1000V voltage points, other voltage accuracy are all 10%. Insulation resistance accuracy is under temperature 040 humidity 40/2075% RHotherwise the accuracy will change.

 

Ground Bond Resistance test

 

No load output voltage

<12v span="">

 

Output current setting

Range

330A

 

Accuracy

±3%×setting+0.2A

 

Current frequency setting

Range

Sine waveform 50Hz/60Hz

 

Accuracy

±0.1%×setting

 

Test time setting

Range

1999s

 

Accuracy

±0.1%×setting+1count

 

Result display mode

Ground resistance or voltage

 

Ground resistance display mode

 

Alarming limits setting

Resistance upper-limit range

3A≤output current≤10A:10600 mΩ

 
  • Quality Engagement
  • Easy change and return
  • Delivery Avaliable
  • Favorable payment

Apply your mail to get promotion information