For full functionality of this site it is necessary to enable JavaScript.

Autrol ATT2100 Digital Temperature Transmitter (RTD,TC)

Type: Temperature Transmitter(TIT), Field Mounting Type
Type sensor: RTD and TC
Accuracy: RTD ±0.17 ℃ , T/C ±0.77 ℃
Input: 
+ RTD input: a=0.00385(KS, JIS, DIN, IEC), a=0.00391(US)
+ Thermocouple input: KSC 1602-1982, JISC 1602-1981, ANSI MC96.1-1982

Protocol: 4 to 20mA, HART 5, Loop Powered
Trim ability: Zero, DAC
Power supply & Load Requirement: 250 to 550 ohm @ 24 Vdc, Loop Powered
Falure Mode: Low ≤ 3.78 mA, High ≥ 21.1 mA
External Buttons: Zero & Span 2 buttons for device configuration
Process Temp. limit: -40 to 85℃ (-104 to 185℉)
Stability: 
+ RTD – 2 years (±0.12% of Reading or 0.15℃ whichever is greater)
+ T/C – 1 years (±0.12% of Reading or 0.15℃ whichever is greater)
3 lines LCD display, Self Diagnostic Function, External Buttons, DAC, Zero Trim, Eng mode
Certificate: Ex d, FM, ATEX, TR CU(EAC), CE, KCs, IP66/67.