HV HIPOT GDCR8600B Leakage Protection Switch Tester (0~600V)

Power supply: 7.4V rechargeable lithium battery (about8.4V when fully charged)

Voltage of test line: <AC600V, relay protection switch test; <AC250V

Rated voltage: AC220V

Leakage current step: 5, 10, 15, 20, 30, 40, 50, 60, 100, 150, 200, 250, 300, 500, 600, 1000 (unit: mA)

AC voltage step: 0~600V

Leakage action time range: 0~999ms

Leakage action time accuracy: 5%rgt±3%dgt

Current accuracy: ±10%rgt±5dgt

Voltage accuracy: ±2%rgt±3dgt

Failure indication: The LCD displays the "999" timeout indication due to too small rated action current or the faulty leakage protector.

Test lead: 1.8m

Test mode: Manual / Automatic mode

Display mode: LCD: 7-inch TFT color touch screen

Size of device: 212*175*76mm

Battery voltage: When the battery voltage drops to 7.0V, the battery voltage is low, please charge in time. The measurements are also accurate at low battery voltage.

Working current: Max. 365mA

Use conditions: -10℃~40℃; <80%RH

Storage conditions: -10℃~60℃; <70%RH

Withstand voltage: ≥100MΩ, AC2kV/rms (between shell and screws)

Standard compliance: IEC1010-1,IEC1010-2-032, pollution degree 2,CAT III (600V) IEC61326 (EMC standard)

Accessories

Main unit x 1 set

Probe test line x 1pc

Test line of alligator clip x 1pc

Test line of power socket x 1pc

Charger x 1pc

Carrying bag x 1pc

User’s guide x 1 copy

Warranty card x 1 copy

Factory test report x 1 copy