PCE-P43 Power Analyzer
Manufacturer: PCE Model: P43 Guarantee: 12 Month - Request a Quotation
- Contact
See more: Equipment Calibration-Inspection & Repair Service
Call for the best priceHanoi city: (024) 35.381.269
Danang city: (023) 63.747.711
Bac Ninh city: (0222)730.39.68
HCM city: (028) 38.119.636
Manufacturer: PCE-UK
Model: PCE-P43
Warranty: 12 months
Technical specifications
Measuring size: Measuring Range Accuracy of Mb.
Alternating current
(L1, L2, L3): 1 A AC;
5 A AC ± 0.2 %
AC voltage
(L1, L2, L3): 2,9 ... 276 V AC (L-N);
10 ... 480 V AC (L-L) ± 0.2 %
± 0.5 %
Frequency
(L1, L2, L3): 47 ... 63 Hz; ±0.1 %
Active power
(L1, L2, L3, ∑): -1.65 ... 1.65 kW; ± 0.5 %
Reactive power
(L1, L2, L3, ∑): -1.65 ... 1.65 kvar; ± 0.5 %
Apparent power
(L1, L2, L3, ∑): 1.4 VA ... 1.65 kVA; ± 0.5 %
Tan (phi)
(L1, L2, L3, ∑): -1.2 ... 1.2; ± 1 %
Power factor:
(L1, L2, L3, ∑) -1 ... 1; ± 0.5 %
Active energy
(created / submitted)
(∑): 0 ... 99,999,999.9 kWh; ± 0.5 %
Reactive energy
(capacitive / inductive)
(∑): 0 ... 99,999,999.9 kvarh; ± 0.5 %
THD: 0 ... 100 %; ± 5 %
Output (numberselectable / max. 4): -20 ... 20 mA
Relay output (numberselectable / max. 4): Turnkey: 250 V / 0.5 A AC
Pulse output Open collector, passive,
Meets EN62053-31;
5000 ... 20000 Imp/kWh progammable
Interface: RS485 Modbus RTU 8N1, 8N2, 8E1, 8O1
Programming interface: USB Modbus RTU 8N2
Dimensions: 45 x 100 x 120 mm
Weight: 300 g
Degree of protection: IP40
Power supply (optional): 85 ... 253 V AC / DC;
20 ... 50 V AC / DC
Operating conditions: -10 ... 55 °C;
0 ... 95 % r.F.
Storage conditions: -30 ... 70 °C;
0 ... 95 % r.F.
Measurement category: CAT III / 300 V
Dilivery Contents
1 x 3-Phase-Power Meter PCE-P43
1 x User manual