Watanabe TZ-1DA Terminal Type AC Current Isolated Transducer (AC Power)

- Base Accuracy : 

±0.2%F.S (5 to 100%F.S)(25ºC±2ºC)

±1.0%F.S (0 to 5%F.S)(25ºC±2ºC)

- Power supply variation : ±0.06 %F.S (±0.5% to the input of 0 to 5%)

- Load resistance variation :±0.1 %F.S (±0.5% to the input of 0 to 5%)

- Frequency variation : ±3 %F.S(Based on 60Hz)

- Temperature characteristic : ±0.02 %F.S/ºC

- Response time : Less than 700msec (0→90%)

- Front adjustments : ±5% for zero and span

- Insulation resistance : Between input and output/power supply ; More than 100MΩ at 500 VDC

- Dielectric strength : Between input and output/power supply ; For 1 min. at 2000VAC

- Power supply voltage : 100 to 240VAC ±10 %

- Consuming current : Less than 20mA (At current output 100VAC); Less than 25mA (At voltage output 100VAC)

- Operating ambient temperature : -5 to 50ºC

- Operating ambient humidity : Less than 90 %RH (No-condensing)

- Storage temperature : -10 to 70ºC

- Storage humidity : Less than 60%RH (No-condensing)

- Case material : ABS resin (Black) 94V-2

- Weight : Approx. 80g