For full functionality of this site it is necessary to enable JavaScript.

Ainuo AN9637H (F) 다기능 전기 안전 분석기 (5000V/40mA, 접지 테스트 32A)

1) AC Hipot test
Rated output capacity: 5000V/40mA,short circuit current >200mA
Voltage range,Accuracy : 0.01~5.00kV,±1.5%
Frequency range,Accuracy:  50Hz or 60Hz,±0.1%
Current range,Accuracy: 0.10~100.00mA,±2%
2) DC Hipot test
Output voltage setting: 100~6000VDC,±2%
 Voltage range,Accuracy: 0.01~6.00VDC,±1.5%
 Frequency range,Accuracy: 0.0~10000uA,±2%
 Current range,Accuracy: 0.1~999.9s,±0.2%
3) Insulation Resistance test
Output voltage setting: 100~2500Vdc,±2%
Resistance range, accuracy: 
+ 1~9999MΩ; 100-499V,1~1000MΩ,±8%
+ 1000~2000MΩ,±12%
+ 500-2500V,1~199MΩ,±2%
+ 200~999MΩ, ± 5%
+ 1000~9999MΩ, ± 15%
4) Ground Bond test
Rated output:  Max output current is 32A,max testing resistance 600mΩ,open-circuit voltage <12v br=""> Current range,accuracy: 2.0~32.0A(hoặc 64A),±2%
Voltage range,accuracy: 3.0~10.0V ,±2%
Resistance range, accuracy: 10.0~99.9~100~600mΩ;±2%
Dimension: 426x133x550mm
Weight: 30 kg

Details

 

Product Detail

Main features
* Latest international standard:Comply with CCC,IEC,EN,VDE,BS,UL,JIS standard requirements,500VA WITHSTAND(AC 5KV/100mA),short-circuitoutput current exceeds 200mA,Ground resistance test current up to 64A,optional resistance or voltage mode.7 kinds of built-innetworking MD card for leakage contace current test,complying with multiple industrial standards.
Latest international standard: Comply with CCC, IEC, EN,VDE, BS, UL,JIS standard requirements. 500VA withstand (AC 5kV/100mA), short-circuit output current exceeds 200mA. Ground resistance test current up to 64A, optional resistance or voltage mode. 7 kinds of built-in networking MD card for leakage contact current test, complying with multiple industrial standards.
Intelligent test: 15 groups of test memories (group name editable), 8-step programming for each group. Product bar code reading and identification, automatically call the test group according to the model/specifications of the products tested. With U-disk to save test data timely.
Auto control: RS232/RS484/GPIB (four), bar code scanner interface, PLC interface, easily forming automation system.
Information management: optional electrical safety monitoring and control system software (ESRS), realizing test process and data management, high test efficiency, convenient for analysis and tracing.

Simplified operation: LCD display, shortcuts, Chinese/English.

Order information:

■AN9638H, 500VA(5000V/100mA) AC/DC withstand voltage, ground test (64A).

■AN9637H, 200VA(5000V/40mA) AC/DC withstand voltage, ground test (32A).

Spec

AC Hipot test

Rated output capacity

AN9638H(F)

500VA5000V/100mA),short circuit current >200mA

AN9637H(F)

200VA5000V/40mA),short circuit current >200mA

Output voltage setting

RangeAccuracy

1005000V±2%×setting+5counts

Output frequency setting

RangeAccuracy

50Hz or 60Hz±0.1%×setting

Alarm current limits setting

Upper-limit rangeAccuracy

0.10100.00mAor 40.00mA),±2%×setting+5counts

Lower-limit rangeAccuracy

0.0009.999mA±2%×setting+5counts

Time setting

Range

0.5999.9s0 is infinite

Ramp up/down time range

0.1999.9s

Accuracy

±0.2%×setting+1count

Measurement

Voltage rangeAccuracy

0.015.00kV±1.5%×reading+1count

Frequency rangeAccuracy

50Hz or 60Hz±0.1%×reading

Current rangeAccuracy

0.10100.00mAor 40.00mA),±2%×reading+2counts

Time rangeAccuracy

0.1999.9s±0.2%×reading+1count

Output voltage waveform, distortion, regulation

Sine wave<2%pure resistance load),<2%×setting+5V)(from empty load to full load

Start voltage setting

0%50%×output voltage setting

Current compensation setting

0.000~100.00mAor 40.00mA),automanual

Arc detection

19 level9 level is optimally sensitive0 is OFF

DC Hipot test

Output voltage setting

RangeAccuracy

1006000VDC±2%×setting+5counts

Alarm current limits setting

Upper-limitAccuracy

0~10000μA±2%×setting+5counts

lower-limitAccuracy

0.0~999.9μA±2%×setting+5counts

Time setting

Range

0.5999.9s0 is infinite

Ramp up time range

0.1999.9s

Ramp down time range

0.3999.9s0 is OFF

Accuracy

±0.2%×setting+1 count

Measurement

Voltage rangeAccuracy

0.016.00VDC±1.5%×reading+1count

Frequency rangeAccuracy

0.010000uA±2%×reading+5count

Current rangeAccuracy

0.1999.9s±<span style="font-size:9.0pt; font-family:"Times New Roman