For full functionality of this site it is necessary to enable JavaScript.

HT MT-200 Continuity/Earth safety tester


- Continuity with 200mA:  0,01Ω÷99.9Ω; ±(5.0% reading + 3 digits)

- Insulation resistance: Test voltage: 50, 100, 250, 500, 1000VDC;±(2.0% reading + 2 digits) 

- Line/Loop Impedance (L-L, L-N, L-PE):  0.01Ω ÷ 199.9Ω; ±(5.0% reading + 3 digits) 

- Earth resistance and ground resistivity: R 0.01Ω ÷ 49.99kΩ;  P 0.60Ωm÷3.14MΩm;  ±(5.0%reading + 3digits)

- Measurement of environmental parameters(with optional probes): 

- Air temperature (°C/°F): -20.0 ÷ 60.0 °C / -4.0 ÷ 140.0 °F

+ Relative humidity: 0% ÷ 100%RH

+ Illuminance (Lux): 0.001lux ÷ 20klux

+ Accuracy: ±(2.0% reading + 2 digits)

- Measurement of main parameters and harmonics (PQA)

+ AC TRMS Voltage: 15.0÷459.9V; ± (1.0%rdg + 1dgt)

+ Frequency: 42.5÷69.0Hz; ±(2.0%rdg + 2dgt)

+ AC TRMS Current: 5% FS ÷ 2999

+ Active Power: 0.000~ 999.9kW

+ Reactive Power: 0.000~ 999.9kW

+ Power Factor: 0.70c÷1.00÷0.70i


Standard accessories

User manual on CD-ROM and quick guide

ISO9000 calibration certificate

Bag BORSA2051

Set of 4 cables, 3 Leads and 4 Alligator Clip Red-Green- Blue UNIVERSALKITG3

Set of 4 rods and 4 cable coils blue-red-green-black KITTERRNE

Rechargeable Battery YABAT0003000

External Battery Charger YABAT0004000

Multi-language software Topview for management TOPVIEW2006