ຮັບສ່ວນຫຼຸດພິເສດຕາມປະລິມານ, ອັບເດດລາຄາຂາຍສົ່ງ ແລະ ການແຈ້ງເຕືອນສິນຄ້າໃໝ່ສົ່ງກົງເຖິງອິນບັອກຂອງທ່ານ.
ໂດຍການສະໝັກສະມາຊິກ, ທ່ານຍອມຮັບ ເງື່ອນໄຂການໃຫ້ບໍລິການ ແລະ ນະໂຍບາຍຄວາມເປັນສ່ວນຕົວ ຂອງພວກເຮົາ.
ເຂົ້າເຖິງຜູ້ຊ່ຽວຊານທີ່ໄດ້ຮັບການຢັ້ງຢືນຂອງພວກເຮົາໂດຍກົງ
ຮັບສ່ວນຫຼຸດພິເສດຕາມປະລິມານ, ອັບເດດລາຄາຂາຍສົ່ງ ແລະ ການແຈ້ງເຕືອນສິນຄ້າໃໝ່ສົ່ງກົງເຖິງອິນບັອກຂອງທ່ານ.
ໂດຍການສະໝັກສະມາຊິກ, ທ່ານຍອມຮັບ ເງື່ອນໄຂການໃຫ້ບໍລິການ ແລະ ນະໂຍບາຍຄວາມເປັນສ່ວນຕົວ ຂອງພວກເຮົາ.
ເຂົ້າເຖິງຜູ້ຊ່ຽວຊານທີ່ໄດ້ຮັບການຢັ້ງຢືນຂອງພວກເຮົາໂດຍກົງ

Temperature range/Ambient temperature range: Temperature range: +7℃ to +25℃
Ambient temperature range: +5℃ to +35℃
Control accuracy (*1)★: ±2.0℃ Compressor On-Off control
Compressor output, Refrigerant: 1.5kW, R407C
Cooling capacity [kW] (50/60Hz) (*2):
Circulation temperature at 10℃: 4.0/4.3
Circulation temperature at 20℃: 4.5/4.7
Pumping capacity★ (50/60Hz) (*3): Max. discharge pressure [MPa]: 0.52
Flow rate [L/min]: 22/31
Motor output [kW]: 0.4
Water bath capacity (at 80% water level): 56L
Safety device/function★: Alarm and warning for water shortage, Compressor pressure abnormal, Compressor overload, Pump overcurrent, Water temperature abnormal, Warning indicator lamp
Connecting pipe diameter (circulating fluid in/out): Rc 1
External dimensions: 570×677×1286 mm
Weight: approx. 178kg
Power Supply (three phase AC200V, 50/60Hz): 20A
Operation current [A] (50/60kHz): 8.2/8.6
Catalog
(*1)There may be a case where the temperature performance cannot be maintained due to environmental temperature, heat load, circulation pipe distance, etc.
(*2)Capacity when the ambient temperature below +25℃.
(*3)Capacity when using tap water. Flow rate when the discharge pressure of CHA-500/900 is at 0.125 MPa and of CHA-1500/2200 at 0.3 MPa.
•Power cable is not included. •Standard products cannot use pure water as circulating fluid.
•The cooling capacity may not be maintained if the unit is placed in direct sunlight and hindrance of exhausting.
•Please ask us when mixing chemicals for water treatment to circulating fluid. •The fee for Delivery and Installing are quoted separately.
★Can upgrade the abilities and add some functions by selecting the following options.
1) To improve accuracy of temperature adjustment (Heater added)
2) To improve capacity of the pump unit (changes to Large flow rate/High head; Several types)
3) To add safety devices (No-fuse breaker and Earth leakage breaker)
4) To change materials such as the stainless steel wetted parts, the circulating fluid piping for the antifreeze, and the ball tap
5) Additional functions (Special order/Option: Remote control box, To reduce noise by fan speed controller)
6) Other (Device fixing brackets)
★Can upgrade the abilities and add some functions by selecting the following options.
1) To improve accuracy of temperature adjustment (Heater added)
2) To improve capacity of pump unit (changes to Large flow rate / High head; Several types)
3) To add safety devices (No-fuse breaker and Earth leakage breaker)
4) To change materials such as the stainless steel wetted parts, the circulating fluid piping for the antifreeze, and the ball tap.
5) Additional functions (Special order/Option: Remote control box, To reduce noise by fan speed controller)
6) Other (Device fixing brackets).