直接联系认证专家

Size: 26.25cm x 14.19cm x 11.93cm (10.3 x 5.6 x 4.7in)
Weight (including batteries)1.6KG (3.5lb)
Battery size, quantity: B290, Li-ion, 10.8V, 2500 mAH, 27 Wh
Ingress Protection: IEC 60529; IP40
Safety: Complies with IEC/EN 61010-1, IEC 61010-2-030, IEC 61010-2-034
Safety rating: CAT III 600 V, CAT IV 300 V
Performance: IEC 61557-1 to IEC/EN 61557-8 and IEC 61557-10
Voltage measurement AC, DC and Frequency
Range: 600V
Resolution: 0.1V
Input Impedance: 320 kΩ
Overload Protection: 660V
Range: 45-66Hz
Resolution: 0.1Hz
Input Impedance: 320 kΩ
Continuity testing (RLO)
Range (Auto ranging): 20Ω/200Ω/2000Ω
Resolution: 0.01 Ω/0.1 Ω/1 Ω
Open Circuit Voltage: >4V
Insulation Resistance measurement (Riso)
Test Voltages: 50-100-250-500-1000V
50V:
Insulation Resistance Range: 10 kΩ to 50 MΩ
Resolution: 0.01 MΩ
Test Current: 1 mA @ 50 kΩ
100V:
Insulation Resistance Range: 10 kΩ to 20 MΩ
Resolution: 0.01 MΩ
Test Current: 1 mA @ 100 kΩ
100V:
Insulation Resistance Range: 20 kΩ to 100 MΩ
Resolution: 0.1 MΩ
Test Current: 1 mA @ 100 kΩ
250V:
Insulation Resistance Range: 10 kΩ to 20 MΩ
Resolution: 0.01 MΩ
Test Current: 1 mA @ 250 kΩ
250V:
Insulation Resistance Range: 20 kΩ to 200 MΩ
Resolution: 0.1 MΩ
Test Current: 1 mA @ 250 kΩ
500V:
Insulation Resistance Range: 10 kΩ to 20 MΩ
Resolution: 0.01 MΩ
Test Current: 1 mA @ 500 kΩ
500V:
Insulation Resistance Range: 20 kΩ to 200 MΩ
Resolution: 0.1 MΩ
Test Current: 1 mA @ 500 kΩ
500V:
Insulation Resistance Range: 200 kΩ to 500 MΩ
Resolution: 1 MΩ
Test Current: 1 mA @ 500 kΩ
1000V:
Insulation Resistance Range: 100 kΩ to 200 MΩ
Resolution: 0.1 MΩ
Test Current: 1 mA @ 1MΩ
1000V:
Insulation Resistance Range: 200 kΩ to 1000 MΩ
Resolution: 1 MΩ
Test Current: 1 mA @ 1MΩ
Insulation pretest
Insulation Safety pretest: Connections from the tester to L, N and PE are required
Surge Protection Device (SPD) Insulation RAMP Test (Varistor Test) IEC 61643-11
Test Voltage: 500V:
Voltage ranges: Step Ramp 0V to 500V
Resolution: 1V
Test Current: 1mA
Accuracy: ± (1.5 % + 3 digits)
Test Voltage: 1000V:
Voltage ranges: Step Ramp 0V to 1000V
Resolution: 1V
Test Current: 1mA
Accuracy: ± (1.5 % + 3 digits)
Insulation Monitoring Devices (IMD) IEC 61557-8
Range: 1 kΩ to 10 kΩ
Resolution: 1 kΩ
Range: 10 kΩ to 100 kΩ
Resolution: 10 kΩ
Range: 100 kΩ to 3 mΩ
Resolution: 100 kΩ
Please note: > 1 MΩ only available with voltages >100 V
Loop and line impedance (ZI No Trip and Hi Current)
Range setting: 10 Ω
Resolution: 0.001 Ω
Accuracy: Hi Current mΩ mode: ± (2 % + 35 digits)/No Trip (2&3 wire) mode: ± (3 % + 6 digits)
Range setting: 20 Ω
Resolution: 0.01 Ω
Accuracy: Hi Current mode: ± (2 % + 4 digits)
Range setting: 200 Ω
Resolution: 0.1 Ω
Accuracy: No Trip mode: ± (3%)/Hi Current mode: ± (2%)
Range setting: 2000 Ω
Resolution: 1 Ω
Accuracy: ± 6%
Prospective Earth Fault Current (PEFC) Prospective Short Circuit Current (PSC)
Range: 0.0-99.9%
Resolution: 0.1%
Accuracy: Consider accuracy of line impedance measurement(s)
Note: Voltage drop reading is calculated from line impedance measurement and entered current rating
RCD tests, RCD types tested
AC (General, no delay)
AC (Time delay)
A, F (General, no delay)
A, F (Time delay)
B, B+ (General, no delay)
B, B+ (Time delay)
RDC-DD,RCD,A/EV,RCD,B/Mi
GFCI