For full functionality of this site it is necessary to enable JavaScript.
EMIN.VN
0
Product image

Metrel MI 3340 PAT Testers (200 mA; 50V, 100V, 250V, 500V)

ModelMI 3340
P/NMI 3340 AlphaEE XA
Contact
Secure Checkout
Quality Engagement
Easy change and return
Delivery Available

Continuity / Protective earth resistance

Continuity (200 mA) (Measuring range/Resolution/Accuracy):

0.00 Ω … 19.99 Ω / 0.01 Ω / ±(2 % of reading + 2 D)

20.0 Ω … 99.9 Ω / 0.1 Ω / ± 3 % of reading

100.0 Ω … 199.9 Ω / 0.1 Ω / ± 5 % of reading

200 Ω … 1999 Ω / 1 Ω / ± 5 % of reading

Insulation Resistance (Riso, Riso-S)

Insulation resistance (50 V, 100 V, 250 V, 500 V) (Measuring range/Resolution/Accuracy):

0.00 MΩ … 19.99 MΩ / 0.1 MΩ / ±(3 % of reading + 2 D)

20.0 MΩ … 99.9 MΩ / 0.1 MΩ / ± 5 % of reading

100.0 MΩ … 199.9 MΩ / 0.1 MΩ / ± 10 % of reading

Output voltage (Um) (Measuring range/Resolution/Accuracy): 0 V … 600 V / 1 V / ±(3 % of reading + 2 D)

Substitute Leakage Current

Substitute Leakage Current (Isub, Isub-S) (Measuring range/Resolution/Accuracy):

0.00 mA … 1.99 mA / 0.01 mA / ±(3 % of reading + 3 D)

2.00 mA … 19.99 mA / 0.01 mA / ± 5 % of reading

Differential Leakage Current (Idiff) (Measuring range/Resolution/Accuracy):

0.00 mA … 1.999 mA / 0.01 mA / ±(3 % of reading + 3 D)

2.00 mA … 19.99 mA / 0.01 mA / ± 5 % of reading

Touch Leakage Current (Itou) (Measuring range/Resolution/Accuracy):

0.000 mA … 1.999 mA / 1 µA / ±(3 % of reading + 3 D)

2.00 mA … 19.99 mA / 0.01 mA / ± 5 % of reading

PE Leakage Current (Ipe):

0.000 mA … 1.999 mA / 1 µA / ±(3 % of reading + 3 D)

2.00 mA … 19.99 mA / 0.01 mA / ± 5 % of reading

Power

Power (Active) (Measuring range/Resolution/Accuracy):

0 W … 19.99 W / 0.01 W / ±(5 % of reading + 5 D)

20 W … 199.9 W / 0.1 W / ± 5 % of reading

200 W … 1999 W / 1 W / ± 5 % of reading

2.00 kW … 3.70 kW / 10 W / ± 5 % of reading

Voltage (U) (Measuring range/Resolution/Accuracy):

0.0 V … 199.9 V / 0.1 V / ±(3 % of reading + 10 D)

200 V … 264 V / 1 V / ± 3 % of reading

Frequency (Freq):

0 Hz (DC) / Indicative

15.0 Hz … 499.9 Hz / 0.1 Hz / ±(0.2 % of reading + 1 D)

Mains supply: 115 V / 230 V AC, 50 Hz / 60 Hz

Max. power consumption: 30 VA (without load on test socket)

Overvoltage category: CAT II / 300V

Protection classification: Class I (mains), Class II (battery)

Display: 4.3 inch colour TFT touch screen (480 x 272 pixels)

Communication: Bluetooth, USB 2.0

Dimensions (w × h × d): 15 cm × 8 cm × 28 cm

Weight: 1.7 kg