INPUT
Rated voltage: 220 VAC
Voltage range: 120 ~ 275 VAC
Phase: Single-phase (2 wires + ground)
Rated frequency: 50/60 Hz (40 ~ 70 Hz)
Power factor: ≥ 0.99
Generator compatible: Yes
OUTPUT
Capacity: 10 kVA / 9 kW
Voltage: 220/230/240 VAC ± 1%
Phase: Single-phase (2 wires + ground)
Frequency: Synchronized with input: 50/60 Hz ± 4 Hz or 50 Hz ± 0.05 Hz (battery mode)
Efficiency: 94% (98% in ECO mode)
Overload capacity:
105% ~ 125% for 1 minute
125% ~ 150% for 30 seconds
150% for 0.5 second
Output connection: Terminal box
BYPASS MODE
Automatically switches to bypass mode in case of: overload, UPS fault, low battery level
BATTERY
Battery type: 12 VDC, sealed (maintenance-free)
Backup time: > 4 minutes
Battery recharge time: 90% capacity in 8 hours
INTERFACE
Control panel: Start button / Self-test / Alarm mute / Power-off button
Status LEDs:
Utility mode
Battery mode
Bypass mode
Load level
Battery level
Fault indication
Communication port: RS232, expansion slot
Management software:
Power management and automatic shutdown software: Winpower / Webpower
Supports operating systems: Windows, Unix, Linux, Sun
Transfer time: 0 ms
OPERATING ENVIRONMENT
Operating temperature: 0 ~ 40 °C
Operating humidity: 20% ~ 90%, non-condensing
Cooling system: Forced air cooling fan
DIMENSIONS / WEIGHT
Dimensions (W x D x H) (mm): 248 x 500 x 616
Net weight (kg): 62.1