Temperature range (*1): -10℃ to +80℃
Ambient temperature range: +5℃ to +35℃
Control accuracy (*2): ±0.5℃ , Heater PID control
Compressor output, Refrigerant: 750W, R404A
Cooling capacity (at 50Hz) (*3): approx. 1.3kW
Heater output: 3kW
Temperature setting display: Digital system (setting/display switching system)
Safety device/function: Short/Over current breaker, Alarm and warning for compressor, High and Low temperature, Alarm and warning for pump motor, Temperature sensor abnormality diagnosis circuit, Alarm for replenishing liquid, Low-water cut off, Phase-reversal relay
Other Functions: Temperature check monitor, Remote temperature setting, Temperature monitor signal output, Safety device actuation signal output, External temperature sensor connection (*4)
Water bath capacity (*5): approx. 26L ( water level 80%)
Applicable pump unit: P-320, P-420, P-520
Dimensions (Pump unit is not included): 407×565×996Hmm
Weight (Pump unit is not included): approx. 75kg
Power Supply (Pump unit is not included): Three-phaseAC200V/20A 50/60Hz,MAX22A: Need a step-down transformer
Operation current (Pump unit is not included): 15A
Standard Accessory: Power cord, Drain hose × 1 pc, Connector for signal × 1 pc, Metal fittings
Catalog
(*1)When setting below +7℃, please be sure to use antifreeze (Please ask us for details).
(*2)Performance may not be maintained due to the heating medium, environmental temperature, heat load, circulation pipe distance, etc.
(*3)Capacity when using tap water and the circulating fluid temperature at 10℃. The capacity varies with the pump unit mounted. The capacity decreases when the ambient temperature is above +30℃.
(*4)External temperature sensor (φ4 × 250 mm) is available as an option.
(*5)Due to the structure not being sealed, the circulation liquid may evaporate and reduce depending on the set temperature and heating medium type.