Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts

RATIO MEASUREMENT
Total Range: 0.75 – 20,000 : 1
Max. errors (0.75 .. 2,500) : ± 0.10 % ± 1d @ 8 V .. 230 V
Max. errors (2,501 .. 5,000) : ± 0.10 % ± 1d @ 40 V .. 230 V; ± 0.15 % ± 1d @ 8 V
Max. errors (5,001 .. 10,000) : ± 0.10 % ± 1d @ 80 V .. 230 V; ± 0.20 % ± 1d @ 8 V .. 40 V
Max. errors (10,001 .. 15,000) : ± 0.15 % ± 1d @ 80 V .. 230 V; ± 0.30 % ± 1d @ 8 V .. 40 V
Max. errors (15,001 .. 20,000): ± 0.30 % ± 2d @ 160 V .. 230 V; ± 1.00 % ± 2d @ 40 V .. 80 V
Measuring voltage: 8 V, 40 V, 80 V, 160 V , 230 V or by external source (8V .. 240 V)
Measuring frequency : 45 Hz – 65 Hz
Range selection: full automatic
PHASE ANGLE MEASUREMENT
Range (one phase) : - 9.9 ° to + 9.9 °
Range (three phase) : - 179.9 ° to + 180 °
Max. error : ± 0.1 ° ± 2 digit
Mag.current measurement : 1 mA – 2000 mA ± 1 mA
MULTIPLEXER
Connections HV : 1U, 1V, 1W, 1N / H0,1,2,3 Amphenol
Connections LV: 2U, 2V, 2W, 2N / X0,1,2,3 Amphenol
Connections ext. excitation : 8 V – 240 V AC, STASEI 5
Error detection : Contact- and stability errors displays: HV / LV too low; bad line stability
Set point input : using front panel, via RS232 or chipcard
Deviances : shown on display, via RS232
Start of measurement : using front panel, via RS232 or IEEE - 488
Display : 256 x 128 pixel LC display, backlight
Result format : vectorgroup, actual phase, actual tapposition, ratio and deviation, phase angle and deviation, exiting current, deviation ref. to setpoints
Measuring Time: 5 ... 20 s depending on line noise/distortion
Measurement Storage: ca. 2000 sets of data on internal memory
Data Transfer: direct or later on with 4167F-XFER - Program
Correct Connections : tested before each measurement
Ports : USB, RS232C (full device control) printer (parallel, ANSI standard, optional)
Temperature Operating:: -10° .. 50°C
Storage: : -20° ... 65°C
Humidity : 0 ... 90% (Storage 95%) non condensing
EMC, Safety, Vibration : CE , IEC61010-1 , ASTM D 999.75
Dimensions, Weight : 490 x 400 x 190 mm (WxDxH, mobile ABS rugged case), approx. 10 kg without cables
Power Supply : 230VAC +10% -15% (196 - 250VAC) / 48..62Hz