EEC SE 7440 Electrical Safety Analyzer (0.000-40.00mA)

REPLACE MODEL:  Associated Research HypotULTRA 7804

INPUT:

• Voltage (AC): 200-240V

• Apparent Power: 600VA

• Frequency: 50/50Hz+/-5%

AC WITHSTAND VOLTAGE:

• Output Rating (AC): 5kV/40mA

• Output Voltage Range: 0-5.00kV

• Voltage Resolution: 0.01kV

• Voltage Accuracy: +/-(1% of setting + 0.5% of range)

• Current Measurement Range (Total): 0.000-40.00mA

• Current Resolution (Total): 0.001/0.01/0.1mA

• Current Accuracy (Total): 

0.000-4.000mA: +/-(2% of reading + 3 counts)

3.50-100.0mA: +/-(2% of reading + 6 counts)

DC WITHSTAND VOLTAGE:

• Output Rating (AC): 6kV/10mA

• Output Voltage Range: 0-6.00kV

• Voltage Resolution: 0.01kV

• Voltage Accuracy: +/-(1% of setting + 0.5% of range)

• Current Measurement Range: 0.0nA-10mA

• Current Resolution: 0.1nA/0.001uA/0.01uA/0.1uA/0.001mA/0.01mA

• Current Accuracy: 

0.0-400.0nA/0.350-4.000uA/3.50-40.00uA: +/-(2% of reading + 10 counts) Low range is ON

35.0-400.0uA/0.300-4.000mA/3.5-10.00mA: +/-(2& of rading + 2 ocunts)

INSULATION RESISTANCE:

• Output Rating (AC): 6kV/5GΩ

• Output Voltage Range: 10-6000V

• Voltage Resolution: 1V

• Voltage Accuracy: +/-(1% of setting + 0.5% of range)

• Resistance Measurement Range: 0.100MΩ-50GΩ

• Resistance Resolution: 0.001/0.01/0.1/1MΩ

• Resistance Accuracy: 

0.05-999.9MΩ under 10-29V: +/-(15% of reading + 2 counts)

0.05-999MΩ under 30-499V: +/-(7% of reading + 2 counts)

0.100-999.9MΩ under 500-6kV: +/-(2% of reading + 2 counts)

1Ω-9.999GΩ under 500-6kV: +/-(5% of reading + 2 counts)

10Ω-50GΩ under 500-6kV: +/-(15% of reading + 2 counts)

CONTINUITY (Optional):

• Output Rating (AC): 1A for 1.000Ω, 0.1A for 10.00Ω, 0.01A for 100.0Ω, 0.001A for 1kΩ, 0.0001A for 10kΩ

• Resistance Measurement Range: 0.000-10kΩ

• Resistance Resolution: 0.001/0.01/0.1/1Ω

• Resistance Accuracy: +/-(1% of reading + 3 counts)

GROUND BOND:

• Output Rating (AC): 32A/600mΩ/8V

• Output Current: 1.00-32.00A

• Current Resolution: 0.01A

• Current Accuracy: +/-(2% of setting + 0.5% of range)

• Output Voltage: 3.00-8.00V

• Voltage Resolution: 0.01V

• Voltage Accuracy: +/-(2% of setting + 0.5% of range)

GENERAL:

• Display: 4.3" Color Display (Touch Panel)

• Interface: Standard USB & RS232, Optional Ethernet, GPIB

• Dimension (WxHxD): 430x88.1x400 mm

• Weight: 15kg