For full functionality of this site it is necessary to enable JavaScript.
EMIN.VN
0
Product image

Metrel MI 3122 Standard set Single-Functional Testers (10 mA; ...; 1000 mA)

ModelMI 3122 Standard set
문의하기
안전한 결제
품질 보장
간편 교환 및 반품
배송 가능

RCD testing

Nominal residual current (A, AC): 10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 1000 mA

Test current shape: Sine-wave (AC), pulsed (A)

RCD type: G (non-delayed), S (time-delayed)

Test current starting polarity: 0 ° or 180 °

Voltage range: 50 V ÷ 264 V (45 Hz ÷ 65 Hz)

Contact voltage:

0.0 ÷ 19.9 V / 0.1 V / (-0 % / +15 %) of reading ± 10 digits

20.0 ÷ 99.9 V / 0.1 V / (-0 % / +15 %) of reading

Trip-out time: 0 ÷ 300 ms / 1 ms / ±3 ms

Trip-out current:

0.2xI∆N ÷ 1.1xI∆N (AC type) / 0.05xI∆N /±0.1xI∆N

0.2xI∆N ÷ 1.5xI∆N (A type, IDN ≥30 mA) / 0.05xI∆N / ±0.1xI∆N

0.2xI∆N ÷ 2.2xI∆N (A type, IDN <30 mA) / 0.05xI∆N / ±0.1xI∆N

Fault loop impedance (no disconnecting device or FUSE selected):

0.00 ÷ 9.99 Ω / 0.01 Ω / ±(5 % of reading + 5 digits)

10.0 ÷ 99.9 Ω / 0.1 Ω / ±(5 % of reading + 5 digits)

100 ÷ 999 Ω / 1 Ω / ± 10 % of reading

1.00 kΩ ÷ 9.99 kΩ / 10 Ω / ± 10 % of reading

Fault loop impedance (RCD selected - no trip out of RCD):

0.00 ÷ 9.99 Ω / 0.01 Ω / ±(5 % of reading + 10 digits)

10.0 ÷ 99.9 Ω / 0.1 Ω / ±(5 % of reading + 10 digits)

100 ÷ 999 Ω / 1 Ω / ± 10 % of reading

1.00 kΩ ÷ 9.99 kΩ / 10 Ω / ± 10 % of reading

Line impedance:

0.00 ÷ 9.99 Ω / 0.01 Ω / ±(5 % of reading + 5 digits)

10.0 ÷ 99.9 Ω / 0.1 Ω / ±(5 % of reading + 5 digits)

100 ÷ 999 Ω / 1 Ω / ± 10 % of reading

1.00 kΩ ÷ 9.99 kΩ / 10 Ω / ± 10 % of reading

TRMS voltage monitor, Frequency

0 V ÷ 550 V / 1 V / ±(2 % of reading + 2 digits)

10.0 Hz ÷ 499.9 Hz / 0.1 Hz / ±(0.2 % of reading + 1 digit)

Phase rotation: 100 VAC ÷ 550 VAC / Result displayed 1.2.3 or 3.2.1

GENERAL DATA

Power supply: 6 x 1.5 V batteries or rechargeable batteries, size AA

Battery life: Typical 20 h

Overvoltage category: 600 V CAT III, 300 V CAT IV

Protection classification: Double insulation

Degree of protection: IP 40

Memory: 1900 measurements

Connectivity: RS232 and USB

Weight: 0.93 kg (without batteries)

Dimensions (W x H x D): 14 cm x 8 cm x 23 cm


Instrument MI 3121 Insulation / Continuity tester

Soft hand strap

Universal test cable 3 x 1.5 m

Test tips, 2 pcs (black, red)

Alligator clips, 2 pcs (black, red)

Power supply adapter + 6 NiMH AA rechargeable batteries

Instruction manual on CD

Short instruction manual

Product verification data

Handbook “Guide for testing and verification of low voltage installations” on CD

Datasheet

혜택 소식 받아보기

대량 할인, 도매 가격 업데이트 및 신제품 소식을 이메일로 받아보세요.

구독하면 당사의 서비스 이용약관개인정보 처리방침에 동의하는 것으로 간주됩니다.

빠른 지원

인증된 전문가에게 직접 연결