Sensor Body Dimensions: 86 mm D x 121 mm H (3.4 in x 4.8 in)

Rear thread 1” BSP/NPT

Weight: 1.2 kg (2.7 lb)

Measurement range: 300 mm to 6 m (11.8in to 19.7ft)

Frequency: 75kHz

Beam Angle: <10°

Effective Beam Angle (using DATEM): 3°

Accuracy: 4 mm (0.2 in) 

Resolution: 2 mm (0.08 in) 

Housing Material: Valox 357 PBT (Polybutylene terephthalate)

Temperature

Compensation: Automatic, internal temperature sensor, ± 0.5 °C/°F

Transducer Cable

Requirements: Twin screened. Integral cable length 5 m, 10 m, 20 m or 30 m (16.4 ft, 32.8 ft, 65.6 ft, 98.4 ft)

Operating Temperature

Range: 40 °C to +80 °C (-40 °F to +176 °F) process temperature

Ingress Protection: IP68 to BS EN 60068-2-17:1995 and BS EN 60529 (Nema 6P available)

Approvals: See EC Declaration of Conformity in the manual

Hazardous Area Approval: ATEX; Ex ia Zone 0 and FISCO

Power: Bus-powered, per IEC 61158-2; 20mA (general purpose or I.S. version) 20mA 18-24 V DC

Update Time: 1 to 2 seconds at 20mA current loop

Programming: PA modem; Simatic PDM, EDDL, FDT/DTM on request. PC interface 2-wire loop powered from PC or laptop. No

external power is required.

Outputs: Profile 3.0.2, Class A with I&M functionality