Automatic circuit breaker tester UPA-1 is designed for testing and ampere-second characterization of automatic AC current circuit breakers. The device allows registering the value of the supplied current and timing the automatic circuit breaker switching interval.

UPA-1 is a mobile device, which could be easily transported to a required testing location.

UPA-1 operates on the principle of varying the power in the primary circuit of the matching power transformer and, respectively, varying the output current, flowing through the automatic circuit breaker under the test. Power regulation could be done either through an external regulator (RNO or VR) or through a built-in thyristor controller.

 

  • Technical Specifications

Characteristic

Value

Single-phase AC power supply voltage, V

220±22

Power supply frequency, Hz

50±1

Maximum output current when powered from 220 V AC circuit, kA

1,2

Test current measurement range, kA

0,10...1

Reduced error of the test current measurement, %

±3

Absolute error of the current flowing time and the switching off time measurement in the range from 50 ms to 990 ms, ms, max

±20

Reduced error of the current flowing time and the switching off time measurement in the range from 1 s to 7200 s, %, max

±3

Continuous running time under the maximum current, s, min

10

Maximum consumed power, kVA

5

Net weight of IT-1 (current supply), kg, max

13

Net weight of the control unit (without flexible busbars), kg, max

3

Net weight of the flexible busbar (length 1 m, cross-section 110 mm2), kg, max

1,2

Dimensions of the control unit, mm, max

340х210х140

Dimensions of the IT-1, mm, max

250х220х115

Lifespan, years, avg

10

  •  
  • Operating Conditions

The device is designed for an indoors operation under the following conditions:

Condition

Value

Air temperature, °С

from -35 to +35

Relative humidity, %, up to

80 at +20° С

Atmospheric pressure, kPa (mm hg)

84,0 – 106,7 (630 – 800)

 

  • Package Contents

Component

Quantity

UPA-1 control unit

1

Current source IT-1

1

Flexible busbar with cross-section 110 mm2 (length 1 m)

2

Flexible wire (2 m)

4

RNO connection outlet

1

Power cable UPA-1

1

Fasteners for connecting busbars, sets

1

RNO (Inom = 12 A)

Optional*

Cable for connecting RNO to UPA-1

Optional*

 

Documentation

 Manual

1

  • * Delivery terms of RNO are discussed separately.