Fluke 1736 三相功率记录仪(1000V /±(0.2%+ 0,01%))

Voltage
- Current: Direct input
+ i17xx-flex 1500 12: 150A/±(1% + 0,02%); 1500A/±(1% + 0,02%)    
+ i17xx-flex 3000 24: 300A/±(1% + 0,03%); 3000A/±(1% + 0,03%)
+ i17xx-flex 6000 36: 600A/±(1,5% + 0,03%); 6000A/±(1,5% + 0,03%)
+ Đầu kìm i40s-EL: 4A/±(0,7% + 0,02%); 40A/±(0,7% + 0,02%)
Frequency: 42,5 Hz to 69 Hz/±(0,1%)
Auxillary input: ±10 V dc/±(0,2% + 0,02%)
THD on voltage: 1000%/±0,5
THD on current: 1000%/±0,5
Voltage harmonics 2nd to 50th: 1000V,  ≥ 10 V: ±5% of reading; < 10 V: ±0,5V
Current harmonics 2nd to 50th: Defined by accessory, ≥ 3% of current range: ±5% of reading, < 3% of current range: ±0.15% of range
Unbalance: 100%/±0,2
IP rating: 50

Details

Manual

Specifications
Accuracy
Parameter Range Resolution Intrinsic Accuracy at Reference Conditions (% of Reading +% of Full Scale)
Voltage 1000 V 0.1 V ±(0.2% + 0.01%)
Current: Direct input i17xx-flex 1500 12" 150 A 0.1 A ±(1% + 0.02%)
1500 A 1 A
i17xx-flex 3000 24" 300 A 1 A ±(1% + 0.03%)
3000 A 10 A
i17xx-flex 6000 36" 600 A 1 A ±(1.5% + 0.03%)
6000 A 10 A
i40s-EL clamp 4 A 1 mA ±(0.7% + 0.02%)
40 A 10 mA
Frequency 42.5 Hz to 69 Hz 0.01 Hz ±(0.1%)
Auxillary input ±10 V dc 0.1 mV ±(0.2% + 0.02%)
Voltage min/max 1000 V 0.1 V ±(1% + 0.1%)
Current min/max Defined by accessory Defined by accessory ±(5% + 0.2%)
THD on voltage 1000% 0.1% ±0.5
THD on current 1000% 0.1% ±0.5
Voltage harmonics 2nd to 50th 1000 V 0.1 V ≥ 10 V: ±5% of reading
< 10 V: ±0.5V
Current harmonics 2nd to 50th Defined by accessory Defined by accessory ≥ 3% of current range: ±5% of reading
< 3% of current range: ±0.15% of range
Unbalance 100% 0.1% ±0.2
Intrinsic Uncertainty ±(% of reading +% of range)¹
Parameter Influence quantity iFlex1500-12 iFlex3000-24 iFlex6000-36 i40S-EL
150 A / 1500 A 300 A / 3000 A 600 A / 6000 A 4 A / 40 A
Active Power P PF ≥ 0.99 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Active Energy Ea
Apparent power S 0 ≤ PF ≤ 1 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Apparent Energy Eap
Reactive power Q 0 ≤ PF ≤ 1 2.5% of measured apparent power
Reactive Energy Er
Power Factor PF - ±0.025
Displacement Power Factor
DBF/cosϕ
Additional uncertainty in% of range¹ VP-N>250 V 0.015% 0.0225% 0.0225% 0.015%
¹Range = 1000 V x Irange
Reference conditions:
  • Environmental: 23 °C ±5 °C, instrument operating for at least 30 minutes, no external electrical/magnetic field, RH <65%
  • Input conditions: Cosϕ/PF=1, Sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10%.
  • Current and power specifications: Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V Input current: I > 10% of Irange
  • Primary conductor of clamps or Rogowski coil in center position
  • Temperature coefficient: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C

 

Electrical Specifications
Power Supply
Voltage range 100 V to 500 V using safety plug input when powering from the measurement circuit
100 V to 240 V using standard power cord (IEC 60320 C7)
Power consumption Maximum 50 VA (max. 15 VA when powered using IEC 60320 input)
Efficiency ≥ 68.2% (in accordance with energy efficiency regulations)
Maximum no-load consumption < 0.3 W only when powered using IEC 60320 input
Mains power frequency 50/60 Hz ±15%
Battery Li-ion 3.7 V, 9.25 Wh, customer-replaceable
On-battery runtime Four hours in standard operating mode, up to 5.5 hours in power saving mode
Charging time < 6 hours
Data Acquisition
Resolution 16-bit synchronous sampling
Sampling frequency 10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input signal frequency 50/60 Hz (42.5 to 69 Hz)
Circuit types 1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, Currents only (load studies)
Data storage Internal flash memory (not user replaceable)
Memory size Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events¹
¹The number of possible logging sessions and logging period depends on user requirements.
Basic Interval
Measured parameters Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging interval User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging time min/max values Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms
Demand Interval (Energy Meter Mode)
Measured parameters Energy (Wh, varh, VAh), PF, maximum demand, cost of energy
Interval User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Power Quality Measurements
Measured parameter Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD
Averaging interval 10 min
Individual harmonics 2nd to 50th harmonic
Total harmonic distortion Calculated on 50 harmonics
Events Voltage: dips, swells, interruptions, current: inrush current
Triggered recordings Full cycle RMS updated every half cycle of voltage and current (Urms1/2 according to IEC61000-4-30)
Waveform of voltage and current
Standards Compliance
Harmonics IEC 61000-4-7: Class 1
IEEE 519 (short time harmonics)
Power quality IEC 61000-4-30 Class S, IEC62586-1 (PQI-S device)
Power IEEE 1459
Power quality compliance EN50160 (for measured parameters)
Interfaces
USB-A File transfer via USB flash drive, firmware updates
Max. current: 120 mA
WiFi File transfer and remote control via direct connection or WiFi infrastructure
Bluetooth Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1738 or 1736 upgrade option)
USB-mini Data download device to PC
Voltage Inputs
Number of inputs 4 (3 phases and neutral)
Maximum input voltage 1000 Vrms, CF 1.7
Input impedance 10 MΩ
Bandwidth (-3 dB) 42.5 Hz - 3.5 kHz
Scaling 1:1 and variable
Measurement category 1000 V CAT III/600 V CAT IV
Current Inputs
Number of inputs 4, mode selected automatically for attached sensor
Input voltage Clamp input: 500 mVrms/50 mVrms; CF 2.8
Rogowski coil input 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range
Range 1 A to 150 A / 10 A to 1500 A with thin flexible current probe i17XX-flex1500 12"
3 A to 300 A / 30 A to 3000 A with thin flexible current probe i17XX-flex3000 24"
6 A to 600 A / 60 A to 6000 A with thin flexible current probe i17XX-flex6000 36"
40 mA to 4 A / 0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth (-3 dB) 42.5 Hz - 3.5 kHz
Scaling 1:1 and variable
Auxiliary Inputs
Number of inputs 2
Input range 0 to ±10 V dc, 1reading/s
Scale factor (available 2014) Format: mx + b (gain and offset) user configurable
Displayed units (available 2014) User configurable (7 characters, for example, °C, psi, or m/s)
Wireless Connection
Number of inputs 2
Supported modules Fluke Connect® 3000 series
Acquisition 1 reading/s
Environmental Specifications
Operating temperature -10 °C to +50 °C (14 °F to 122 °F)
Storage temperature -20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F)
Operating humidity 10 °C to 30 °C (50 °F to 86 °F) max. 95% RH
30 °C to 40 °C (86 °F to 104 °F) max. 75% RH
40 °C to 50 °C (104 °F to 122 °F) max. 45% RH
Operating altitude 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage altitude 12,000m
Enclosure IP50 in accordance with EN60529
Vibration MIL-T-28800E, Type 3, Class III, Style B
Safety IEC 61010-1
IEC Mains Input: Overvoltage Category II, Pollution Degree 2
Voltage Terminals: Overvoltage Category IV, Pollution Degree 2
IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V
Electromagnetic compatibility EN 61326-1: Industrial CISPR 11: Group 1, Class A
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
Temperature coefficient 0.1 x accuracy specification/°C
General Specifications
Color LCD display 4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel
Warranty Instrument and power supply: Two-years (battery not included) 
Accessories: one-year 
Calibration cycle: two-years 
Dimensions Instrument: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in)
Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in)
Instrument with power supply attached: 19.8 cm x 16.7 cm x 9 cm (7.8 in x 6.6 in x 3.5 in)
Weight Instrument: 1.1 kg (2.5 lb)
Power supply: 400 g (0.9 lb)
Tamper protection Kensington lock slot
i17xx-flex 1500 12" Flexible Current Probe Specifications
Measuring range 1 to 150 A ac/10 to 1500 A ac
Nondestructive current 100 kA (50/60 Hz)
Intrinsic error at reference condition* ±0.7% of reading
Accuracy 173x + iFlex ±(1% of reading + 0.02% of range)
Temperature coefficient over operating temperature range 0.05% of reading/°C 0.09% of reading/°F
Working voltage 1000 V CAT III, 600 V CAT IV
Probe cable length 305 mm (12 in)
Probe cable diameter 7.5 mm (0.3 in)
Minimum bending radius 38 mm (1.5 in)
Output cable length 2 m (6.6 ft)
Weight 115 g
Probe cable material TPR
Coupling material POM + ABS/PC
Output cable TPR/PVC
Operating temperature -20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F)
Temperature, non-operating -40 °C to +80 °C (-40 °F to 176 °F)
Relative humidity, operating 15% to 85% non-condensing
IP rating IEC 60529:IP50
Warranty One-year
* Reference condition:
  • Environmental: 23 °C ±5 °C, no external electrical/magnetic field, RH 65%
  • Primary conductor in center position
 
     