see also: press article about MIC-10 and MIC-30
- Insulation resistance measurement:
- selected test voltage: any voltage in the 50...1000V range with 10V step,
- automatic measurement in sockets with the UNI-Schuko adapter with possibility of configuring pairs of measured cables,
- continuous indication of insulation resistance or leakage current,
- automatic discharge of capacitance of tested object after the insulation resistance measurement,
- acoustic signalling of five-second periods to facilitate obtaining time characteristics,
- measured test times T1, T2 i T3 to measure one or two absorption coefficients in the 1... 600 sec. range,
- indication of actual test voltage during the measurement,
- protection against measuring live objects,
- three-lead measurement. - Continuity measurement of protective and equipotential conductors according to EN 61557-4 with the >200mA current
- Low-voltage circuit continuity and resistance measurement:
- circuit resistance measurement (<1999 with="" the="" 15ma="" current="" br=""> - quick sound signal if circuit resistance is below 30. - Leakage current measurement.
- Capacitance measurement during the RISO measurement
- Measurement of alternating and direct voltages in the 0...600V range.
- 990 memory cells and wireless data transmission to a computer using the USB - OR-1 adapted.
- Power supply: 4 AA disposable or rechargeable batteries, monitoring of power supply voltage.
- Meters conform to EN 61557.
- type of insulation: double, according to EN 61010-1 and IEC 61557
- measurement category: IV 600V (III 1000V) according to EN 61010-1
- protection class acc. to EN 60529: IP67
Other technical specifications:
- power suply: 4 alkaline batteries or or battery package Ni-MH
- weight: ~1kg
- dimentions: 220 x 100 x 60 mm
Insulation resistance measurement
Measuring range according to EN 61557-2 for UN=50V: 50kΩ...250,0MΩ
Range | Resolution | Accuracy |
0,0...999,9kΩ | 0,1kΩ | ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]* |
1,000...9,999MΩ | 0,001MΩ | |
10,0...99,99MΩ | 0,01MΩ | |
100,0...250,0MΩ | 0,1MΩ |
*for the WS-04 lead
Measuring range according to EN 61557-2 for UN=100V: 100kΩ...500,0MΩ
Range | Resolution | Accuracy |
0,0...999,9kΩ | 0,1kΩ | ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]* |
1, 000...9,999MΩ | 0,001MΩ | |
10,0...99,99MΩ | 0,01MΩ | |
100,0...500,0MΩ | 0,1MΩ |
*for the WS-04 lead
Measuring range according to EN 61557-2 for UN=250V: 250kΩ...2,000GΩ
Range | Resolution | Accuracy |
0,0...999,9kΩ | 0,1kΩ | ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]* |
1,000...9,999MΩ |
0,001MΩ | |
10,0...99,99MΩ |
0,01MΩ | |
100,0...999,0MΩ | 0,1MΩ | |
1,000...2,000GΩ | 0,001GΩ |
*for the WS-04 lead
Measuring range according to PN-EN 61557-2 for UN=500V: 500kΩ...20,00GΩ
Range | Resolution | Accuracy |
0,0...999,9kΩ | 0,1kΩ | ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]* |
1,000...9,999MΩ | 0,001MΩ | |
10,00...99,99MΩ | 0,01MΩ | |
100,0...999,0MΩ | 0,1MΩ | |
1,000...9,999GΩ | 0,001GΩ | ±(4% m.v. + 6 digits) [±(6% m.v. + 6 digits)]* |
10,00...20,00GΩ** | 0,01GΩ |
*for the WS-04 lead
**for the WS-04 lead range to 10GΩ
Measuring range according to EN 61557-2 for UN=1000V: 1000kΩ...10,00GΩ
Range | Resolution | Accuracy |
0,0...999,9kΩ | 0,1kΩ | ±(3% m.v. + 8 digits) |
1,000...9,999MΩ | 0,001MΩ | |
10,00...99,99MΩ | 0,01MΩ | |
100,0...999,0MΩ | 0,1MΩ | |
1,000...9,999GΩ | 0,001GΩ | ±(4% m.v. + 6 digits) |
10,00...99,99GΩ | 0,01GΩ | |
100,0GΩ | 0,1GΩ |
Continuity measurement of protective and equipotential conductors with the 200mA current
Measuring range according to EN 61557-4: 0,10...1999Ω
Range | Resolution | Accuracy |
0,00...19,99Ω | 0,01Ω | ±(2% m.v. + 3 digits) |
20,0...199,9Ω | 0,1Ω | |
200...1999Ω | 1Ω |
±(4% m.v. + 3 digits) |
- Voltage on open terminals: <8V
- Output current at R <2Ω: ISC >200mA: ISC >200mA
- Compensation of test leads’ resistance
- Unidirectional current flow
Low-voltage and resistance measurement
Range | Resolution | Accuracy |
0,0...199,9Ω | 0,1Ω | ±(3% m.v. + 3 digits) |
200...1999Ω | 1Ω |
- Voltage on open terminals: <8V
- Current for closed terminals 5mA < ISC < 15mA
- Sound signal and green LED on when measured resistance < 30Ω ± 50%
- Compensation of test leads’ resistance,
Range | Resolution | Accuracy |
1...999nF | 1nF | ±(5% m.v. + 5 digits) |
1,00...9,99µF | 0,01µF |
- Capacitance value displayed during the RISO measurement
- For test voltages below 100V and measured resistance below 10MΩ, unspecified capacitance measurement error
Measurement of alternating and direct voltage
Range | Resolution | Accuracy |
0,0...299,9V | 0,1V | ±(2% m.v. + 6 digits) |
300...600V | 1V | ±(2% m.v. + 2 digits) |