Output Power: 45kVA
Max AC Output: 450V L-N, 70A/ph
Max DC Output: 0~636V, ±70A
Dimension (W*D*H mm): 800*900*1500
Weight(kg): 460
General Specification
AC input
Voltage: 3P+N+PE, 380VLL±10%(std)
Frequency: 47-63Hz
Efficiency: ≥85%
Power Factor: 0.99
THDi: <3%FS
Output
Output Modes: AC, DC, or AC+DC
Power Level: From 15kVA to 1080kVA
Load Regulation: 0.1%FS
Line Regulation: 0.1%FS
AC Output
Voltage & Current Range (max output per 15KW module):
Max 450V L-N, 70A @ DC~65Hz
Max 375V L-N, 70A @ 65~1000Hz
Max 350V L-N, 70A @ 1000~2000Hz
Max 250V L-N, 60A @ 2000~3000Hz
Max 150V L-N, 50A @ 3000~5000Hz
Phase Angle Range: Phase B/C relative to phase A, 0.0~360.0°
Frequency Range: DC -5000Hz
Small signal bandwidth: 10kHz
THD:
<0.3%FS @15~50Hz (measured at 250V L-N, Resistive Load)
<0.4%FS @50~500Hz (measured at 250V L-N, Resistive Load)
<0.7%FS @500~2000Hz (measured at 250V L-N, Resistive Load)
<1%FS @2000~4000Hz (measured at 100V L-N, Resistive Load)
<2%FS @4000~5000Hz (measured at 100V L-N, Resistive Load)
Harmonic Generation:
Up to 100th @50/60Hz
Harmonic accuracy: 1%FS
Within 50th: total harmonic content ≤ 100%; Within 100th: total harmonic content ≤ 30%
Voltage Slew Rate: ≥5V/us
Current Slew Rate: ≥0.5A/us
Current Peak Factor: 1 ~ 3
Power Accuracy: DC~45Hz: 0.3%FS; 45~70Hz: 0.1%FS; 70~2KHz: 0.3%FS
Voltage Accuracy: DC~45Hz: 0.2%FS; 45~70Hz: 0.1%FS; 70~2KHz: 0.2%FS
Current Accuracy: DC~45Hz: 0.3%FS; 45~70Hz: 0.1%FS; 70~2KHz: 0.3%FS
Frequency Accuracy: 0.01%FS+0.01Hz
Phase Angle Accuracy: DC~45Hz: <1°; 45~70Hz: <0.1°; 70~2KHz: <1°
Power Resolution: 0.001kW
Voltage Resolution: 0.1V
Current Resolution: 0.01A
Frequency Resolution: 0.01Hz (~100Hz); 0.05Hz (>100Hz)
DC Output
Voltage & Current Range (max output per 15KW module): 0~636V, ±70A/ch
Voltage Accuracy: 0.1%FS
Current Accuracy: 0.1%FS
Voltage Ripple: 0.1%FS
AC+DC Mode: Max Power, Voltage and Current are the same as DC Mode
RLC/RCD Load Simulation
R: Range: 0.1~1000Ω. Resolution: 0.1Ω. Accuracy: ±0.1%FS
L: Range: 0.01~500mH. Resolution: 0.01mH. Accuracy: ±0.1%FS
C: Range: 0.001~50mF. Resolution: 1uF. Accuracy: ±0.1%FS
Others
Standard Interface: LAN/RS485/ATI
Protection: OVP, OCP, OPP, OTP
IP Ingress protection: IP21
CE Conformity: EN 62040-1, EN 62040-2
Cooling: Forced Air Cooling
Temperature Operating: 0~40℃ Storage: -20~85°C
Operating Humidity: 20-90%RH (None Condensing)