For full functionality of this site it is necessary to enable JavaScript.
EMIN.VN
0
Product image

COSMOS XP​​-3110 気体検知器

ModelXP​​-3110
原産地Japan
お問い合わせ
安全なチェックアウト
高品質な対応
簡単な交換・返品
配送対応可能

Appropriate equipment to measure gas concentrations fire from 0-10/0-100LEL (lower explosive limit one)
Most appropriate to monitor the risk of fire.
Shown with the latest techniques with the technical loop.
Having integrated corrections to 05 fire gases (optional from factory).

- The gas measuredCH4C3H8C4H10Ethanol, H2, acetylene... (please describe the type of gas to be measured)
- Principle of measurement: Sensor heating the catalyst
- Sampling method: Extraction patterns
- Measuring range: 0-100% LEL
- Accuracy (under defined conditions): ± 5% of measuring range
- Limit alarm: 20% LEL.
- Display:
  LCD (with backlight). Show number0-100% LEL.
Display bar number: automatically switching between the two levels shown.
0-10% LEL (Low)
0-100% LEL (H)
-Alarm signals:
Gas alarmsirenflashing red lights
Error: sirensflashing red lights, shown on
LCD screen.
- Design explosionExibd II BT3
- Operating temperature20-50 degrees C
- Power source: 4xAA - Alkaline dry battery
- Operating timeup to 20 hours
- Dimensions (WxHxD): 82x162x36mm
- Weight~ 450g (excluding battery)
- Standard accessory attached to the unit
- Softwith the first air duct sampling samples 1m, 4 AA alkaline dry batteryair filter paper
- Optional accessories2-30m gas sampling tubesthe dilute gas, software download data (CD software disc and USB cable)