Measurement & Accuracy

Component/Range

String Voltage:  20 to 800V, Accuracy: +/- 0.5%

Battery voltage: 2V, 6V, 12VAccuracy: +/- 0.1%

Battery resistance: 50 to 65535uΏAccuracy: +/- 2%, 1uΏ

Battery temperature: -5°C to 99.9°CAccuracy: +/- 1°C

String current: 0 to 1000AAccuracy: +/- 2%

Ambient temperature: -5°C to 99.9°C, Accuracy:+/- 1°C


Environmental Measurements: Operating temperature: -10°C to 50°C; Humidity: 5% to 95%

Monitoring Capability

+ Maximum batteries on a single String: 180

+ Control module string maximum: 6

+ Control module battery maximum: 360

+ Include 1 Relay and 2 Dry Contact Inputs

Specifications

+ Battery types: 2V, 6V, 12V (capacity less than 3000AH)

+ Insulation: 2000 VAC

+ Weight (Coordinator): 0.3 Kg

+ Weight (Battery Sensor): 75 g

+ Weight (String Sensor): 80 g

Controller Module Communication Interfaces: 

+ Serial Comm. Port: RS485 Modbus/RTU

+ RJ45 Ethernet Comm. Port: SNMP, Modbus/TCP

+ RJ22 Module Comm. Port: COM1-COM3 UART

Power Requirements

+ Base coordinator unit: 14-36 VDC 40W, external power supplies available

+ Battery sensor: < 13mA (1.2V, 2V) or 7mA (6V, 12V) from battery

+ String sensor: 10.8 to 13.8VDC, 2W, power from control module

Approvals & Certifications:

+ EMC Certification: CISPR 11, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-11

+ Compliance: CE & FCC

Reliability: Auto reboot trigger: Build-in WDT; MTBF: 100,000 hours    