Gastec 8LL 塩素クイック測定検出器チューブ Cl2(0.025〜2ppm)
メーカーGastec(このブランドの他の製品を見る)
Model8LL
お問い合わせ
安全なチェックアウト
高品質な対応
簡単な交換・返品
配送対応可能
Indicator: 0.1~1ppm
Measuring Range:
+ 0.025 to 0.05 ppm, Number of Pump Strokes 2
+ 0.05 to 1.0 ppm, Number of Pump Strokes 1
+ 1.0 to 2.0 ppm, Number of Pump Strokes 1/2
Sampling Time: 2 minute per pump stroke
Colour Change: White → Pale Green
Reaction Principle: Cl2 + ABTS → Pale green products
Coefficient of Variation: 10% (for 0.05 to 0.2 ppm), 5% (for 0.2 to 1.0 ppm)
Nr. of tests: 10
Pump: GV-100S/110S
Performance
| Measuring Range |
|
|||
| Number of Pump Strokes |
|
|||
| Correction Factor |
|
|||
| Sampling Time | 2 minutes per pump stroke | |||
| Detecting Limit | 0.005 ppm (n=2) | |||
| Colour Change | White → Pale Green | |||
| Reaction Principle | Cl2 + ABTS → Pale green products | |||
| Coefficient of Variation | 10% (for 0.05 to 0.2 ppm), 5% (for 0.2 to 1.0 ppm) | |||
| Shelf Life | 1 Year | |||
| Corrections for temperature & humidity | Unnecessary | |||
| Store the tubes in the refrigerator to keep at 10ºC (50ºF) or below. | ||||
Possible coexisting substances and their interferences (NOTE)
| Substance | Concentration | Interference | Change colour by itself to |
| Ammonia | No | No | |
| Carbon monoxide, Carbon dioxide | No | No | |
| Hydrogen chloride | No | No | |
| sulphur dioxide | No | No | |
| Nitrogen dioxide, Chlorine dioxide | + | Pale green | |
| Halogens | + | Pale green | |
| Hydrogen sulphide | No | No | |
| Organic vapours | No | No |
| Calibration gas generation | Permeation tube method |
| TLV-TWA | TLV-STEL | Explosive range |
| 0.5 ppm (2014) | 1 ppm (2014) | - |
お得な情報を受け取る
数量割引、まとめ買い価格の更新、新製品情報をメールでお届けします。
登録することで、当社の利用規約およびプライバシーポリシーに同意したものとみなされます。
クイックサポート
認定専門家へ直接アクセス