GOLDSOL VLF-40TD High Voltage Test Set (1–40 kV AC/DC)
Power supply: 220 V ± 10% AC (110 V can be customized), 50/60 Hz, single phase.
AC output voltage: 1–40 kV peak (28.2 kV RMS).
DC output voltage: 1–40 kV.
Output frequency: 0.1 Hz, 0.05 Hz, 0.02 Hz, 0.01 Hz (automatic variable frequency).
Load capacity: Max. 1.0 μF @ 0.1 Hz; max. 10.0 μF @ 0.01 Hz.
Frequency stability: Fluctuation < 0.5%.
AC voltage measurement accuracy: ±3%.
AC voltage measurement resolution: 0.1 kV.
AC current measurement accuracy: ±3%.
AC current measurement range: 0–20 mA; resolution: 0.1 mA.
Positive and negative voltage peak error: ≤3%.
Voltage waveform distortion: ≤3%.
Construction: Integrated device.
Ambient operating conditions: Indoor and outdoor temperature: -10 °C to +50 °C.
Humidity: ≤85%.
Technical Specifications of VLF tgδ Test (Optional)
tgδ test voltage range: 1–40 kV.
Measurement voltage accuracy: 1%.
Dielectric loss test frequency: 0.1 Hz.
Measurement range: 0.01 × 10⁻³–655.35 × 10⁻³.
Dielectric loss accuracy: 1 × 10⁻⁴.
Dielectric loss resolution: 1 × 10⁻⁵.
Capacitance measurement range: 0.001–10 μF.
Capacitance measurement resolution: 0.001 μF.
Current measurement range: 0–20 mA; Tan Delta/PD test curve.
Current resolution: 0.1 mA.
Insulation resistance: 1 MΩ–65,535 MΩ (if exceeded, the device will prompt the excess).
Insulation resistance resolution: 1 MΩ.
Main Technical Specifications of VLF PD Test (Optional)
Partial discharge measurement range: 0.1 pC–10,000 pC.
Partial discharge detection resolution: 1 pC.
PD measurement accuracy: 3%.
Capacitance range: 0.001–10 μF.
Sampling bits: 12 bits.
Sampling speed: 200 MS/s; U, PD & tgδ curve.
Test voltage: 0 to rated value (40 kV).
Display of instantaneous and peak PD values.
Display of discharge inception voltage and discharge extinction voltage.
Discharge pulse frequency: 1–2,000 kHz.
Real-time output of the partial discharge evaluation report.
DC Leakage Current Measurement (Optional)
DC output rated voltage: 40 kV max.
DC voltage accuracy: 3%.
Leakage current range: 0–2,000 μA (0–20 mA can be customized).
DC current resolution: 1 μA.
DC current accuracy: 3%.