For full functionality of this site it is necessary to enable JavaScript.
EMIN.VN
0
Product image

Kingsine PMC72S 三相多機能パワーメータ

お問い合わせ
安全なチェックアウト
高品質な対応
簡単な交換・返品
配送対応可能

Electrical characteristics

Measure Type: 3P3W ACsystem,3P4W ACsystem

Sampling rate: 128 points per cycle

Data refresh rate: 1S

Measure accuracy:

+ Current: ±0.2%FS

+ Voltage: ±0.2%FS

+ Power: 0.5S

+ Frequency: ±0.001Hz

+ DC input(AI): 0.5% FS

+ DC output(AO): 0.5% FS

Input voltage characteristics

+ Measure Voltage: 3 *220/380V(Directly input) 3 * 57.7/100V(PT secondary side)

+ Allowed overload capability: 1.2 times/continuous

+ Input resistance: 300KΩ/phase

Input current characteristics

+ Measure current: 5A (CT Secondary side)Or 1A (CT Secondary side)

+ Allowed Overload capability: 1.2 times/continuous

+ Input resistance: <0.1Ω

Binary input

+ Working valtage: 15 VDC

+ Input resistance: 12KΩ

+ Isolation valtage: 2KV

Relay Output

+ Node type: Mechanical contact

+ Node capability: 220 VAC/5A、30 VDC/5A

4-20mA DC input measurement

+ Measure current: 4-20mA

+ Allowed Overload capability: 1.2 times/continuous

+ Input resistance: 10Ω

+ Isolation voltage: 2KV 0-5V

DC input measurement

+ Measure voltage: 0-5V

+ Allowed Overload capability: 1.2 times/continuous

+ Input resistance: 12.5KΩ

+ Isolation voltage: 2KV 4-20mA

DC output

+ Open-circuit: 15VDC

+ Load capability: ≤600Ω

+ Isolation voltage: 2KV

Power supply

+ AC: 85~264 VAC/45-65Hz

+ DC: 100~375 VDC

+ Power consumption: < 3W

Mechanical performance

Weight: <0.5kg

IP protection Level: Meter Panel IP52

                                Meter Host IP30

Dimension(Host): 75 X 75 X 113 mm

Working temperature

+ Display screen: -20~70℃

+ Meter: -25~70℃

Storage temperature:

Meter+display screen: -40~85℃

Relative humidity: 5% - 90%RH, No condensation

PMC72S Guide for selection of power parameter measurement and control instrument

Model specificationPMC72S-----
① Model code
157.7/100V Rated measurement voltage5A Rated measurement current
257.7/100V Rated measurement voltage1A Rated measurement current
3220/380V Rated measurement voltage5A Rated measurement current
4220/380V Rated measurement voltage1A Rated measurement current
② Model code
1Power supply85~264 VAC/45-65Hz100~300 VDC
③ Model code
0Without DI
22 Channels DI
④ Model code
0Without relay output
1Optional 1 Channel relay output
⑤ Model code
abab is a 2 integer,a means AI01 port optional for AI/AO modules,b means AI02 port optional for AI/AO
0none
1 -0-5VDCanaloginputmeasure(AI)
2 -4-20mA DC analog input measure(AI)
3 -4-20mA DC analog output(AO)For example:ab=00,Means AI01 port is not equipped with AI/AO module,AI02 port is not equipped with AI/AOmodule
ab =01,Means options 0-5V DC analog input measure;

For exampleOrder modelPMC72S-3-1-2-1-02 
Means PMC72S rated measure 220/380V5Aworking power supply as 85~264 VAC/45-65Hzoptional with 2channels binary input(DI)1channels relay output1channel 4-20mA DC analog input measure (AI01 port),1 channel 4-20mA DC analog input measure(AI02 port)

お得な情報を受け取る

数量割引、まとめ買い価格の更新、新製品情報をメールでお届けします。

登録することで、当社の利用規約およびプライバシーポリシーに同意したものとみなされます。

クイックサポート

認定専門家へ直接アクセス