Technical Features

Test chamber: With calcium silicate lining, flap with fire resistant glazing, extractable mounting plate for sample holder, exhaust with light measurement system

Radiant panel: Gas fueled radiant panel

Burner system: Stainless steel row gas burner with pneumatic shifting option with ignition device, flame detector and check valve

Sample holder: Stainless steel insertion holder for easy sample positioning

Gas installation: With digital gas flow controllers, pressure controllers and magnetic valves

Exhaust hood: Stainless steel hood with smoke measurement ports

Measuring and control unit: Colour touchscreen, measuring and control modules and USB interface

Software: Data link acquisition and analysis software


Radiant heat measurement:

The distance burned until flame-out is reached is converted, by calibration, into an equivalent critical radiant flux in kW/m2

Radiant panel: Tiles are conducted to give a maximum critical radiant heat flux of 10.9 kW/m2, optionally extendable up to 25.0 kW/m2


Smoke measuring system:

Smoke measuring system according to DIN 50055 mounted on a separate frame at the exhaust stack


Supplies

Power supply: 230 V 50 Hz single phase

Fuel gas: Propane

Compressed air: Dry industrial air 2 atm


Configuration Including

Pyrometer: 1 to 9 µm sensitivity

Thermocouple: Type K

Heat flux meter: Schmidt Boelter heat flux meter (25 mm) 0 to 15 kW/m2


General

Dimensions: 60 × 200 × 200 h (mm)