Onset T-ACT-0750-100 100 Amp Accu-CT Split-Core Current Transformer 333mV Sensor (333.33 mV AC)

ModelT-ACT-0750-100
P/NT-ACT-0750-100
お問い合わせ
安全なチェックアウト
高品質な対応
簡単な交換・返品
配送対応可能

Accuracy: ±0.75% from 1% to 120% of rated primary current

Phase angle: ±0.5 degrees (30 minutes) from 1% to 120% of rated current

Accuracy standards: IEEE C57.13 class 1.2 and IEC 60044-1 class 1.0

Primary rating: 5 to 250 Amps, 600 Vac, 60 Hz nominal

Output: 333.33 mVac at rated current (100 Amps)

Operating temperature: -30°C to 55°C

Safe: integral burden resistor, no shorting block needed, unless otherwise noted

Standard lead length: 8 ft (2.4 m), 20 AWG

UL recognized, CE mark, RoHS

Width: 2.38 inches

Height: 2.40 inches

Thickness: 0.90 inches

Window: 0.78 inches

The Accu-CT split-core current transformer offers outstanding accuracy and one-handed operation. For use with HOBO H22, U30, and RX3000 Series Data Loggers