Sensors: Infrared
Measuring Ranges: 0 – 5000 ppm
Lower Detectable Limit (LDL): 2% of full scale
Response Time (T-90): 45 Seconds
Life Expectancy: 5 years with normal service 
Accuracy: +/- 5% of full scale (0.5% volume for oxygen)
Location: Indoor Class I, Div. 2
Temperature: -4°F to 122°F -20°C to 50°C
Humidity: 0 – 99% RH, non condensing
Housing
Housing J Box : Cast aluminum explosion proof
Sensor: Plastic or aluminum
Controls
Zero: Sets transmitter output to 4 mA with zero output from sensor
Span: Sets transmitter output to 20 mA with full scale output from sensor
Output: 4 – 20 mA signal
Operating Voltage: 19 VDC to 30 VDC
Controllers: Compatible with the following controllers: Beacon 110, Beacon 200, Beacon 410, and 800, also PLC and DCS systems