Wrindu RDXB(WJ)-450kW Transformer Induced Voltage Withstand and Partial Discharge Test System (450kW)

ModelRDXB(WJ)-450kW
お問い合わせ
安全なチェックアウト
高品質な対応
簡単な交換・返品
配送対応可能

Rated input power supply: 380V±10% (three-phase); 50Hz

Rated output power: 450kW

Rated output capacity: 450kVA

Rated output voltage: Single phase 0~350V

Output phase: single phase

Adjustable frequency range: 20Hz~300Hz

Output frequency resolution: 0.01Hz

Output frequency instability: ≤0.05%

Output voltage waveform: Sine wave; waveform distortion rate ≤ 1.0%

The amount of partial discharge: ≤10pC

System working hours: 90min

Insulation level: 1.2 times the rated voltage withstand voltage 1min

Noise level: ≤85dB

Quality factor: Q>100(f=30Hz)

AC power frequency converter: 450kW (push-pull linear amplification)

Product composition

NO.

Name

Specification

Quantity

1

No partial discharge AC power frequency converter and control box

RDXB(WJ)-450kW

1 unit

2

No partial discharge excitation transformer

RDB(WJ)-450kV/2*±10/35

Low voltage:2×300/350V/400V

1 unit

3

No partial discharge compensation reactor

RDBK(WJ)-35kV(6H/8A,3H/12A、25kV/1H/20A)90min

4 units

4

No partial discharge capacitive voltage divider and coupling capacitor

FRC(WJ)- 100kV/300pF

1 unit

5

Partial discharge comprehensive analyzer

RDPDD-104H

1 unit

Scope of application and characteristics of the device

1. Suitable for the partial discharge and induction withstand voltage test of power transformer of 400kV/350MVA and below;

2. AC power frequency converter adopts a linear amplification circuit; sine wave output with small waveform distortion.

3. Automatic and steady voltage adjustment.

4. Overvoltage, overcurrent and other protection functions make the device safe and reliable.

5. Optical fiber is used to transmit high voltage signal, which completely isolates the high-voltage and low-voltage circuits.

6. With automatic and manual control modes.

7. Synchronized voltage, current and frequency display.

8. It has the function of resonant withstand voltage test.

9. With automatic resonant frequency search function, automatic sweeping of multiple frequency segments can be set.