인증된 전문가에게 직접 연결
인증된 전문가에게 직접 연결

General information
Range of application: Vibration monitoring on small machines: power < 300 kW, speed 120 ... 600 rpm
Frequency range: 2 ... 10000 Hz
Vibration measuring range: 0 ... 45 mm/s (RMS)
Number of measuring axes: 1
Temperature measurement: -30°C ...80 °C (only IO-Link)
Parametrisation options: Vibration (Veff / aPeak); hysteresis / window; switch points; switching logic; fault indication; self-test; frequency filter
Outputs / inputs
Switching output: 2x Normally closed (NC)
Comment Switching output: Normally open/ normally closed parameterisable via IO-Link
IO-Link: Yes
Electrical data
Operating voltage: 10 ... 30 V DC
Voltage type: Direct voltage (DC)
Electrical design: PNP, NPN*, *IO-Link parameterisation
Current carrying capacity max.: 100 mA
Voltage drop max.: 2 V
Current consumption max.: 250 mA
Protection class: III
Short-circuit protection: Yes
Overload-proof: Yes
Reverse polarity protection: Yes
Mechanical data
Type of installation: Threaded pin
Material of housing: V4A (1.4404)
Protection rating:
IP67
IP68
IP69k
Electrical connection: M12, 4-pin, Contacts gold-plated
Accuracy
Linearity deviation: < 2 %
Accuracy (temperature measurement): ± 2.5 K + (0.2 x (ambient temperature - surface temperature))
Accuracy: < 4 kHz ±10 %; < 10 kHz < 3 dB
Ambient conditions
Ambient temperature min.: -30 °C
Ambient temperature max.: 80 °C
Accessories included with delivery: 2 threaded pins