FUZRR ES7050 Power Distribution Line Fault Search Instrument (0 - 40 mA, 0 - 3 kV, 0 - 36 mA)
Output AC Detection Current: 0 to 40 mA (Accuracy: ±2 mA)
Output AC Detection Voltage: 0 to 3 kV
Output DC Ground Impedance Current: 0 to 36 mA (Accuracy: ±2 mA)
Output DC Ground Impedance Voltage: 0 to 2.7 kV
Calibration Impedance Current Accuracy: ±1.0 mA
AC Detection Signal Output Accuracy: ±1.0 mA
Measuring Range (Grounding Resistance): ≤ 120 kΩ
Detection Line Length: ≤ 100 km
Ground Impedance Measurement Range: 0 to 120 kΩ
Ground Impedance Measurement Accuracy: ±5% ±2 kΩ
Effective Maximum Output Power: 95 W
Protection & Alarm
Signal Loop Open Circuit Protection Time: ≤ 5 s
Signal Output Loop Integrity Detection Protection Time: ≤ 5 s
Detection Signal Fluctuation Alarm Threshold: ±2 mA
Open Circuit Recognition Current Limit: ±2 mA
Low-Voltage Alarm: 24.5 V
Discharge Cut-off Voltage: 23 V
Power & Battery
Rated Working Voltage: 25.9 VDC
Working Voltage Range: 23 to 29.4 V
Battery Capacity: 29.4 V / 9 Ah
Power Maintenance Time: > 1.2 hours at maximum output power
Auto Power-Off Time: 0.5 to 10 minutes (adjustable)
Environmental & Mechanical
Display Mode: Display with backlight function
Working Temperature: 5 ℃ to 45 ℃
Device Size (L x W x H): 465 x 345 x 185 mm
Fast fault search, the fault point error does not exceed 1 meter
The signal source uses a carp battery power, small volume, light weight, easy to carry, comes with power supply, no generator requires
The operator operates through the insulating rod, and the interior of the device is equipped with overvoltage protection to ensure that the operation is safe and reliable
Output AC detection current: 23 ℃ ± 5 ℃
Output AC detection voltage: 0 ~ 3KV
Output DC ground impedance current: 0 ~ 36 ± 2mA
Output DC ground impedance voltage: 0 ~ 2.7KV
Ground impedance current accuracy: ±1mA
AC detection signal output accuracy: ±1mA