What is the acceptable grounding resistance value for a lightning protection system?

2026년 02월 09일 15시 11분 52초

When installing lightning protection or completing electrical systems for houses and factories, the most frequently asked question is: what is the acceptable grounding resistance? This number is not just for reference; it is directly related to the level of safety when leakage current or lightning surges reach the ground.

In reality, many jobs have been found where the electrical resistance to ground is measured at the next address but the final inspection or measurement step is omitted. Only when a problem occurs is it discovered that the resistance to ground is significantly higher than the permissible level.

How is earth resistance understood?

Simply put, ground resistance reflects how quickly or slowly current flows into the ground. The more conductive the soil, the faster the current flows, and the lower the risk of dangerous voltage buildup.

This value varies depending on the soil type, moisture content, compaction, groundwater level, and even the placement of grounding rods. Moist clay soils generally yield much lower results than dry sandy soils or rocky ground.

Why is it necessary to measure ground resistance after construction?

Completion of construction does not mean that requirements have been met. Two grounding systems may look identical, but the measured values ​​can differ significantly. Measurement is the only way to know the system's current state.

Furthermore, earth resistance can gradually increase over time due to dry soil, oxidized grounding rods, or degraded connections. This is why large construction projects often undergo periodic inspections.

In the field, measuring instruments such as the Kyoritsu 4105A or Hioki FT3151 are widely used due to their fast operation and suitability for measuring both single piles and multi-pillar systems. For larger projects, the Hioki FT6031-50 allows measurements without disconnecting the connections, saving inspection time.

What is the appropriate resistance rating for a lightning protection system?

According to applicable standards, direct lightning protection systems are generally recommended to have a resistance level not exceeding 10 ohms. This is sufficient to dissipate lightning surges into the ground instead of propagating back into the building.

In areas with poor soil conditions such as rocky or dry sand foundations, the resistance may be higher. In such cases, additional grounding rods, increased embedment depth, or soil treatment may be necessary to reduce resistance.

- Low-voltage residential and industrial electrical systems

With commonly used voltages of 380V and 220V, requirements are usually stricter.

Houses and small workshops typically accept a voltage not exceeding 10 ohms. Systems with higher power or a concentration of electrical equipment require even lower voltages, usually not exceeding 4 ohms, to limit the risk of leakage current.

- Repeated grounding of the neutral point

In distribution lines, each repeated grounding point is typically required to not exceed 10 ohms. If geological conditions are difficult to handle, a higher level may be acceptable, but the number of grounding points must be increased to better disperse the current.

- Anti-static grounding

Fuel depots, chemical plants, or areas with flammable materials require extra attention to static electricity. For these systems, the grounding resistance is usually allowed to be higher, commonly below 100 ohms, as long as the charge does not accumulate over time.

- Common grounding for multiple systems

When power, telecommunications, and lightning protection share a single grounding system, the requirements become more stringent. A common level is not to exceed 1 ohm to avoid voltage differences between systems in case of a fault.

Ground resistance measuring devices are being used.

In practical grounding system testing, each measurement purpose requires a suitable type of equipment. The most common is the ground resistance meter, which uses the 3-pole method for stable and reliable results, and is chosen by many field engineers. For geological surveys, the 4-stake soil resistivity meter helps assess soil characteristics before construction.

For quick checks of an operating system, a ground resistance clamp meter offers convenience as it doesn't require disconnection. Additionally, some multimeters still integrate basic ground resistance measurement functionality, suitable for applications that don't require extremely high accuracy. Brands like Fluke, Hioki, and Kyoritsu are currently widely used in this category of equipment.

관련 뉴스

Realizing a High-Performance RF System: The Combination of MATLAB and Tabor Proteus
2026년 06월 26일 10시 32분 59초

Bridging the gap between theoretical simulation and actual hardware implementation remains the greatest challenge in advanced engineering projects. In fields such as radar, 5G/6G, and quantum computing, a lack of synchronization between the design environment and operational hardware often prolongs development timelines

Downtime Doesn't Strike Suddenly: Many Factories Lose Hundreds of Hours of Production by Overlooking Subtle Warning Signs
2026년 06월 25일 14시 15분 17초

For many factories, downtime is often viewed as an unexpected event that strikes during a production shift. In reality, however, the situation is different. Before a motor fails, a variable frequency drive (VFD) reports an error, or a production line requires an emergency stop, the equipment typically emits multiple warning signals—such as abnormal temperature rises, excessive vibration, degraded power quality, or unstable communication performance. These indicators can persist for days or even months before an actual breakdown occurs

Micsig MOIP Series: Comprehensive testing solution for high-power three-phase inverters
2026년 06월 22일 11시 36분 21초

The widespread adoption of wideband semiconductor components such as SiC and GaN in photovoltaic inverters, motor drives, and automotive charging systems has driven the switching frequency and power density of three-phase inverters to unprecedented levels. However, this development has also brought with it severe measurement challenges: high voltages, intense electromagnetic interference, and the requirement for ultra-fast switching signal capture at the nanosecond scale

Does living near a BTS base station affect your health?
2026년 06월 22일 11시 03분 15초

Is it dangerous to live near a BTS base station? Find out the assessments from the WHO, ICNIRP, Vietnamese regulations, and the actual electromagnetic radiation levels in residential areas.

혜택 소식 받아보기

대량 할인, 도매 가격 업데이트 및 신제품 소식을 이메일로 받아보세요.

구독하면 당사의 서비스 이용약관개인정보 처리방침에 동의하는 것으로 간주됩니다.

빠른 지원

인증된 전문가에게 직접 연결