System Data
Memory capacity: 2 MB flash ring buffer
Memory expansion:Internal card slot for microSD card, optional 4 GB microSD card, formatting via the SMARTCONTROL manager
Storage rules: Cyclical or based on conditions
Calculations: Mean value generation, heating and cooling quantities, timer programs, limit value monitoring, calculator, integral value generation
Programming: Each channel separately, graphic programming using function blocks with the SMARTCONTROL manager
Time Battery-backed real-time clock
System monitoring: Watchdog timer
Control keys: F1, reset on the system PCB
SMARTCONTROL Standard
Housing material: Steel sheet metal
Dimensions: 226 x 210 x 70 mm
Mounting: Screw mounted
Protection: IP 20
Weight: 1.5 kg
Mains power:
SMARTCONTROL can be operated with 12 ... 24 V DC.
Power consumption*:
– Basic PCB < 2.5 W
– Expansion for LON interface module: additionally max. 1 W
– Expansion for input/output module for 24 channels: additionally max. 10 W
Input: 100 ... 240 V AC, 50 ... 60 Hz
Output: 12 V DC
Option: External power pack (primary switched mode) Z301U
Operating conditions: 5 ... 50 °C, no condensation
Real Time Clock Battery
Lithium cell (replaceable without the use of tools and data loss): CR 2032 3 V; for the preservation of time and date
Permanent operation: Replacement every 5 years
Non-operating time/ lengthy storage periods: Replacement every 2 years
*For detailed specifications, please refer to the datasheet.