AC voltage output: 4 channels:0-130V continuously adjustable 6 6V by default
Output precision: Accuracy:0~5V Accuracy error ≤±2mV, 5V~120V Accuracy error ≤±0.1%±2mV; Resolution:1mV
Carrying capacity: ≥30VA/phase
Response time: Voltage 5V~130:THD%≤0.5%,The voltage rise and fall time is less than 100µs
Phase: 0-360° continuously adjustable; Accuracy 0.2°; Resolution 0.1°
AC current output: 3 channels:0-10A
Output precision: Accuracy:0.2~0.5A, Error ≤2mA, 0.5~10A Accuracy error ≤0.1%±2mA; Resolution:1mA
Current output time:
T330 current output time calculation formula is as follows:
(Ia*Ia+Ib*Ib+Ic*Ic)*t = 600 seconds
Typical current setting output time is as follows:
Ia=1A, Ib =0A, Ic=0A output time is 600 seconds
Ia=1A,Ib =1A,Ic=1A output time is 200 seconds
Ia=5A,Ib=5A,Ic=5A output time is 90 seconds
Ia=10A, Ib=10A, Ic=10A output time is 6 seconds
Carrying capacity: ≥20VA/phase
Response time: Current 0.5A~Imax:THD% ≤0.5%; The current rise and fall time is less than 100µs
Phase: 0-360° Continuously adjustable; Accuracy 0.2°; Resolution 0.1°
Output frequency: 0-650Hz, It can simulate 11 harmonics
Accuracy: Frequency range:10-65Hz Accuracy<1mHz; 65 Hz ~250Hz Accuracy<10mHz
Opening & Closing volume:
Opening volume:2 channels Isolation voltage is 500V, the null contact is compatible with 32V~250V potential, and the polarity is automatically recognized;
Closing volume:Type of 2 channels closing volume: optocoupler opening, time resolution is 0.1ms.
Adapter: DC 16.8V 5A
Built-in battery & Endurance: Built-in 20 amh lithium battery; Normal use of 8 hours
Instrument size & Weight: Less than 2.75kg(hand-held)size:255x210x78(mm)