HV HIPOT GDCY-100kV/5kJ Impulse Current Test System (±100kV; 5kJ)

ModelGDCY-100kV/5kJ
원산지China
보증1 년
문의하기
안전한 결제
품질 보장
간편 교환 및 반품
배송 가능

• Nominal voltage: ±100kV           

• Rated level voltage: ±100kV

• Rated energy: 5kJ

• Impulse capacitance: 1µF

• Number of Levels: 1

• Rated level capacitance: 3µF(each impulse capacitor 1µF at 100kV, total 1piece)

• Impulse voltage waveform: generated when load capacitance is 300-3000pF.

• T1=1.2µs±30%,  T2=50µs±20%,  standard lightning impulse voltage full waveform of  peak voltage deviation≤3%;

• Standard operation waveform 250±20%/2500±60%. These 2 Impulse voltage  waveform parameters and error are accorded with national requirements of GB311.1and IEC60060 standard.

• Voltage utilization factor: Standard lightning impulse voltage waveform ≥90% when load capacitance is below 1000pF, standard operation impulse voltage waveform≥80% when load capacitance is below 2000pF. 

• Standard operation impulse voltage waveform ≥70%.

• Locking range: level voltage is within the range of 20%-100%rated voltage, positive and negative 

• locking range no less than 25%.

• Out-of-control rate of synchronous discharge: <5%

• Min.output voltage: ≥±20% of rated voltage.

• Instability of discharge voltage: <±1.0%

• Continuous time: Above 2/3 of rated voltage, continuous working when charge and discharge once every 120s. Below 2/3 of rated voltage, continuous working when charge and discharge once every 60s.