Rated output: 

- Frequency error: <±0.01Hz

- Phase error:<±0.2°

- Waveform distortion: <±0.3% (fundamental wave)

- Time error: <40µs

- Output frequency: 20~1000Hz

Power voltage: Allowable range: AC220V±10%,50Hz±10%

Ambient temperature: 

- Use range: 0~40℃

- Storage range: -20~70℃

AC source 

Current: 

- 6 Phase current output (RMS): 0~30A/phase

- 3 Phase current output (RMS): 0~60A/phase

- 6 parallel current output (RMS): 0~180A

- Long-term allowable working value of phase current (RMS): 10A

- Allowable working time of 6 parallel current 180A: 10s

- Accuracy: <±0.2%

- Max. Output power of phase current: 300VA

- Max. Output power of 6 parallel phase current: 1000VA

- Harmonic frequency: 1~20 times

  Voltage: - Phase voltage output (RMS): 0~120V

- Line voltage output (RMS): 0~240V 

- Accuracy: <±0.2%

- Phase/Line voltage output power: 80VA/100VA

- Harmonic frequency: 1~20 times

DC source 

Current:

- Output range: 0~±10A/phase

- Accuracy: <±0.5% 

- Max. Output load voltage: 20V

Voltage: 

- Phase voltage output amplitude: 0~±160V

- Line voltage output amplitude: 0~±320V

- Accuracy: <±0.5%

- Phase/Line voltage output power: 70VA/140VA

Time measurement: Test range: 0.1ms~9999s

Accuracy: <0.1mS

8 Binary input: Idle contact: 1~20mA, 24V(DC)

Electric potential contact: ”0”: 0 ~ +6V; “1”: +11 V ~ +250 V

4 Binary output: DC: 220 V/0.2 A: AC: 220 V/0.5 A

Dimension: 410mm ×360mm ×200mm

Weight: 23kg