AC current output 

Phase current output (effective value): 0-40A

Phase current max. Output power: 420VA

Maximum parallel current output (effective value): 0~120A

Maximum parallel power output: 900VA

Long-term allowable working value of phase current (effective value): 10A

Allowable working time of maximum current: 10s

Frequency range (fundamental wave): 20-1000Hz

Harmonic wave times: 1-20times

Accuracy: 0.5%

AC voltage output 

Phase voltage output (effective value): 0~120V

Line voltage output (effective value): 0~240V

Phase voltage/Line voltage output power: 80VA/100VA

Frequency range (fundamental wave): 20-1000Hz

Harmonic wave times: 1-20times

Accuracy: 0.5%

DC voltage output 

Phase voltage output range: 0~±160V

Line voltage output range: 0~±320V

Phase voltage/Line voltage output power: 70VA/140VA

Accuracy: 0.5%

DC current output 

Output range: 0- ±10A /phase, 0-±30A / parallel

Maximum output load voltage: 20V

Accuracy: 0.5%

Binary input (7channels): Idle contact: 1~20mA, 24V (DC)

Electric potential contact: “0”:0- +6V; “1”: +11 V- +250V 

Binary output (2pairs): DC 220V/0.2A; AC 220V/0.5A

Time measurement 

Measurement range: 0.1ms-9999s; accuracy 0.1ms

Volume and weight

Appearance and size: 400×300×180mm³

Weight of a single machine: 22kg

Supply power: AC 220V±10%,50/60Hz

Environmental temperature: -10℃ ~ +50℃