HV HIPOT GDTF-200/400 AC Resonant Test System for Substation Equipment (0-400kV; 200kVA)
문의하기
안전한 결제
품질 보장
간편 교환 및 반품
배송 가능
Rated output voltage: 0 - 800kV (AC ) or below.
Output frequency: 20 ~ 300Hz.
Waveform: pure sine wave, THD <1.0%.
Max. capacity: 1000kVA and below.
Duty Cycle: Continuous working time 15mins one time at full power output.
Quality factor: 30-90.
Frequency adjustment sensitivity: 0.1Hz, instability <0.05%.
Power Supply: 380/220V ± 15% / 50Hz ± 5%.
Input voltage (V): 380
Output voltage (kV): 0-400
Capacity (kVA): 200
Application scope:
- 110kV GIS and transformer
- 220kV GIS and transformer
Main configurations:
• 10kW Variable frequency source 1 set
• 10kVA Exciting transformer 1 set
• Reactors 100kV/0.5A 4sets
• Capacitive divider 400 kV