EMS Protection

EFT (IEC 61000-4-4): ±4 kV for power

ESD (IEC 61000-4-2): ±8 kV air discharge for random poin

LED Indicators

Status: 1 as power indicator; 4 as alarm indicators

System

Alarm: For both liquid leak detection and cable-break detection

Buzzer: Yes; can be muted by a push button

Liquid Leak Detection

Channels: 4

Liquid Type: Water, 2 µS/cm

Sensor Type: Probe for point detection or cable for line detection

Max. Cable Length: 500 meters

Includes: Liquid leak detection cable and extension cable

Sensitivity Range: 26 kΩ ~ 580 kΩ (rotary switch adjustable)

Cable-break Detection: Yes

For Liquid Leak Detection Cable: CA-LLD-DC100X-Lxxx only

Ethernet

Ports: 1 × RJ-45, 10/100 Base-TX

PoE: Yes

Access Control: ID, password and IP filter

Protocol: Modbus TCP/UDP, MQTT

Power

Reverse Polarity Protection: Yes

Input Range: 10–48 VDC

Consumption: 1.6 W max.

Powered from PoE: Yes, IEEE 802.3af, Class 1

Mechanical

Dimensions (mm): 72 × 95 × 57 (W × L × H)

Installation: DIN-rail mounting

Environment

Operating Temperature: -25 ~ +75 °C

Storage Temperature: -30 ~ +80 °C

Humidity: 10–90% RH, non-condensing