인증된 전문가에게 직접 연결
인증된 전문가에게 직접 연결

* Signal analyzer specification:
+ Operation environment
- Working power: DC40V-300V
- Temperature: -20℃—55℃
- Humility:0—90%
+ DC voltage measurement
- Measurement range:0-300V
- Resolution: 0.1V
- Accuracy: 0.2%
+ AC voltage measurement
- Measurement range: 0-300V
- Resolution: 0.1V
- Accuracy: 0.5%
+ Insulation resistance measurement
- Measurement range: 0-999.9KΩ
- Resolution: 0.1KΩ
- Accuracy: ≤±5%
+ Measurement Bridge:
- Adjustment range: 0mA, 0.25mA, 0.5mA, 1mA, 2mA & 4mA(optional)
- Frequency range: 0.25Hz
+ Grounding detection range: up to 200KΩ
+ Distributed capacitance measurement
- Measurement range: 0-999uF
+ Measurement waveform: square wave & sine wave
+ Working mode: compulsory signal & automatic signal
+ Display: 320×240 pixels TFT
+ Weight and dimension: 0.448kg, 200*145*75mm
* Signal detector specification
+ Grounding resistance measurement
- Measurement range:0-500KΩ
- Resolution: 0.1KΩ
- Accuracy: ≤±10%
+ Frequency spectrum analysis
- Number of channels: 1
- Frequency range: 0.125-12.5Hz
- Resolution: 0.125Hz
+ Display period of current waveform: 8s
+ Measuring range for feeder: 0~2A
+ Current measurement range: -100~+100mA
+ Current resolution: 0.01mA
+ Display: 320×240 pixel TFT
+ Clamp jaw size: Ф30mm, Ф40mm and Ф10mm (optional)
+ Power supply: 5V
+ Weight and dimension: 0.303kg, 215*100*33mm