Leak Control NH3 in Industrial Cold Storage

2026년 10월 16일 16시 35분 37초

Managing refrigeration systems using ammonia (NH3) aims to minimize the risk of poisoning, fires, and explosions, ensuring occupational safety and system operation

Ammonia (NH3) refrigerant leaks in cold storage facilities and food processing plants always present a tough challenge regarding operational safety. Not only do these incidents directly threaten human lives, but they also cause production line disruptions and severe economic losses. Mastering the legal framework, thoroughly understanding technical principles, and equipping specialized monitoring systems are key to protecting modern industrial infrastructure.

What Is an NH3 Cold Storage Facility

An ammonia (NH3) cold storage facility is an industrial refrigeration solution utilizing the natural refrigerant R717 (NH3). It is best suited for large-scale cold storage systems, seafood and agricultural processing plants, and industrial food manufacturing due to its superior thermal efficiency and low operating costs.

Owing to the unique chemical properties of ammonia, this type of cold storage offers powerful advantages but also demands extremely strict technical safety standards.

Legal Framework and Compliance Standards for (NH3) Operation

In Vietnam, the management of refrigeration systems using (NH3) is strictly regulated by legal normative documents to minimize toxicity and explosion hazards:

  • Circular No. 50/2020/TT-BCT: Specifies the National Technical Regulation on Industrial Ammonia (QCVN 07:2020/BCT), applying to the production, storage, transportation, and usage of (NH3) with concentrations ranging from 10% to 35%.

  • Decision No. 3733/2002/QĐ-BYT: Issued by the Ministry of Health, establishing the maximum allowable concentration of NH3 gas in the workplace at 20 mg/m3 (approximately 25 ppm) as an 8-hour time-weighted average (TWA) per work shift.

  • Industrial Fire Protection Standards: Require large-capacity cold storage facilities to integrate automatic emergency ventilation systems, water spray/chemical absorption fire suppression systems, and online toxic gas sensor networks.

Incident Causes and Mechanisms

NH3 leaks typically originate from a loss of system tightness, mechanical failure, or operational errors. Pipelines, welded joints, gaskets, stop valves, and compressor shafts can crack, corrode, or deteriorate over time due to prolonged vibration, pressure fluctuations, and thermal cycling. Additionally, overpressure or improper valve operation can cause refrigerant to escape.

  • Poisoning Mechanism: NH3 readily dissolves in moisture on the eyes and respiratory tract, forming alkaline compounds that irritate and damage tissues. Inhaling high concentrations can cause severe respiratory distress and lung damage. Escaping liquid NH3 at low temperatures can also cause frostbite upon direct contact. The severity depends on gas concentration, exposure time, and area ventilation.

  • Fire and Explosion Hazard: NH3 can ignite when its atmospheric concentration falls within its flammable limits in the presence of an ignition source, such as electrical sparks or hot surfaces. Gas accumulation in enclosed spaces, combined with poor ventilation, increases the risk of fire and pressure buildup during an incident. NH3 may also react dangerously with certain incompatible chemicals.

Preventive Measures and Optimization of Environmental Monitoring Systems

Preventing incidents requires a combination of equipment maintenance, NH3 concentration monitoring, and controlling factors that could trigger poisoning or explosions.

  • Regular Inspection and Maintenance: Monitor the condition of piping, joints, valves, compressors, and pressure vessels; detect early signs of corrosion, abnormal vibration, or seal degradation. Concurrently, test safety relief valves and emergency shut-off mechanisms to mitigate large-scale leak risks.

  • Use of Specialized Equipment: Combine portable single-gas detectors with fixed NH3 sensors installed in compressor rooms, valve stations, and receiver areas. Sensors must be selected for the correct measuring range, regularly inspected, and calibrated alongside motor vibration meter to detect early shaking issues and abnormal concentrations, triggering alarms when preset thresholds are exceeded.

  • Dispersal Control and Fire/Explosion Prevention: Equip emergency ventilation systems, audible/visual alarms, and interlock systems designed to activate solenoid shut-off valve relays, isolate liquid supply valves, and engage directional emergency exhaust fans. Control ignition sources, use electrical equipment compatible with the area's hazardous classification, and prevent gas accumulation in enclosed spaces.

  • Training and Emergency Preparedness: Establish evacuation procedures, area isolation, and incident response protocols; provide appropriate personal protective equipment (PPE) and conduct regular drills. Unqualified personnel lacking proper protective gear must not approach leak points or enter suspected toxic zones.

Emergency Response Procedure

When the monitoring system triggers a red alert, the operating team must execute the following steps precisely:

  1. Isolate the Pipeline: Press the emergency stop button in the central control room to close all main gas stop valves leading from high-pressure receivers.

  2. Activate Auxiliary Infrastructure: Engage the high-pressure water misting system in the compressor area to absorb and dilute the escaping NH3 gas plume, preventing widespread dispersion.

  3. First Aid and Medical Emergency: Move victims out of the toxic zone, perform artificial respiration if necessary, and continuously flush exposed skin/eyes with clean water for at least 15 minutes before transferring them to a medical facility.

관련 뉴스

What Is Fiber Polarity and How Do You Choose an MPO Method?
2026년 11월 14일 11시 35분 16초

Fiber polarity ensures the transmit path connects to the corresponding receive path. For MPO-based duplex channels, the selected method must remain consistent across trunks, cassettes, adapters, and patch cords.

The scent of new wood in a newly handed-over apartment: How to measure and address formaldehyde (HCHO) levels before moving in
2026년 11월 14일 10시 28분 19초

Many people refer to the pungent, acrid odor that emerges when opening a new cabinet as the "smell of new wood," assuming it will simply dissipate after a few days. In reality, however, what is being released could well be formaldehyde—a substance originating from the adhesives used in the pressed-wood panels—and our sense of smell is not a reliable enough gauge to determine the concentration levels present

Guide to Selecting a TCLP Toxicity Characteristic Leaching Procedure Shaker Configuration in Compliance with QCVN 07:2025/BNNMT and TCVN 9239:2012
2026년 11월 13일 17시 23분 39초

Regulation QCVN 07:2025/BNNMT (replacing QCVN 07:2009/BTNMT and QCVN 50:2013/BTNMT) specifies hazardous waste and sludge thresholds based on leachate concentrations. To ensure that analytical results for heavy metals and organic compounds are accepted during ISO/IEC 17025 or VIMCERTS assessments, laboratories must comply with the Toxicity Characteristic Leaching Procedure (TCLP) specified in TCVN 9239:2012, which is equivalent to US EPA Method 1311

Checking the Temperature of Paint and Coating Surfaces After Curing Using an Infrared Thermometer
2026년 11월 13일 16시 11분 22초

An infrared thermometer allows surface temperature measurement without direct contact, making it suitable for products coming out of curing ovens or surfaces that are difficult to access. However, to ensure reliable results for production quality control, it is important to understand the measurement principle and the factors that affect measurements on painted and coated surfaces.

Crowded Gyms and Yoga Studios: How to Manage Air Quality to Retain Members
2026년 11월 13일 15시 07분 40초

Around 6 or 7 in the evening, the gym becomes packed; the music drowns out the sound of heavy breathing, and the air conditioning runs at full blast behind closed doors. At first glance, everything seems fine: the room is cool, the lights are bright, and the equipment is state-of-the-art. Yet, after just a few sessions, regular members begin to feel a heavy-headedness and find themselves running out of breath more quickly eventually, they simply stop renewing their memberships. No one complains about the personal trainers or the exercise machines. The very thing that makes them feel stifled and drives them away is something entirely invisible: the air inside the room

혜택 소식 받아보기

대량 할인, 도매 가격 업데이트 및 신제품 소식을 이메일로 받아보세요.

구독하면 당사의 서비스 이용약관 및 개인정보 처리방침에 동의하는 것으로 간주됩니다.

빠른 지원

인증된 전문가에게 직접 연결