AC voltage input range
5 kV, 10 kV: 90-264 V rms, 47 / 63 Hz, 100 VA
15 kV: 90-264 V rms, 47 / 63 Hz, 200 VA
Battery: 11.1 V, 5.2 A hour, safety rated to IEC 62133:2003
Battery life
Typical capacity is 6 hours continuous @ 5 kV with a 100 MΩ load
Auto power off: Instrument turns off after a few minutes if non-use to conserves battery life
Battery charge time:
2.5 hours from deep discharge
2 hours from normal discharge
30 min. charge: 1 hour continuous test at 100 MΩ, 5 kV
Test voltages: 250 V, 500 V, 1000 V, 2500 V, 5000 V
User defined test voltage: 40 V to 1 kV in 10 V steps
Display range analogue: 100 kΩ to 10 TΩ
Display range digital: 10 kΩ to 10 TΩ
Short circuit current
Essential range: 3 mA nominal – Maximum power regulation technology ensure maximum
power transfer throughout all loads not just at short circuit outperforming many 5 mA testers
Advanced range: 1 mA, 3 mA Default, 6 mA @ 5 kV, 10 kV, 15 kV (6 mA only from mains supply)
Insulation alarm: 100 kΩ to 1 GΩ
Capacitor charge: < 3 s/μF to 5 kV
Capacitor discharge: <250 ms/μF to discharge from 5 kV to 50 V
Capacitance range (above 500 V)
10 nF to 25 μF (5 kV, 10 kV)
10 nF to 50 μF (15 kV)
dependent on measurement voltage
Capacitance accuracy (23 °C): ±10% ±5 nF
Voltage output accuracy: (>200 V, 0 °C to 30 °C): +4%, -0%, ±10 V nominal test voltage at 1 GΩ
Current measurement range: 0.01 nA to 6 mA
Current measurement accuracy (23 °C): ±2% ±0.5 nA at all voltages
Interference (noise) rejection mA rms: 1 mA per 250 V to a maximum of 3 mA
Voltmeter range 30 V to 660 V AC or DC, 50 / 60 Hz
Voltmeter accuracy ±3%, ±3 V
Timer range Up to 99 minutes, 15 second minimum setting
Memory capacity 5½ hours continuous logging every 5 s or 33 logged PI tests, or 350 logged IR tests