Metrel MI 3123 Earth Resistance Tester (0.00~9999Ω)
EARTH RESISTANCE
Earth Resistance (4-wire method / One clamp method):
(Measuring range/ Resolution/ Accuracy)
0.00 Ω ÷ 19.99 Ω / 0.01 Ω / ±(3 % of reading + 3 digits)
20.0 Ω ÷ 199.9 Ω / 0.1 Ω / ±(3 % of reading + 3 digits)
200 Ω ÷ 1999 Ω / 1 Ω / ± 5 % of reading
2000 Ω ÷ 9999 Ω / 1 Ω / ± 10 % of reading
Earth Resistance (Two clamps method):
(Measuring range/ Resolution/ Accuracy)
0.00 Ω ÷ 19.9 Ω / 0.01 Ω / ±(10 % of reading + 10 digits)
20.0 Ω ÷ 30.0 Ω / 0.1 Ω / ± 20 % of reading
30.1 Ω ÷ 39.9 Ω / 0.1 Ω / ± 30 % of reading
SPECIFIC EARTH RESISTANCE
(Measuring range/ Resolution/ Accuracy)
0.0 Ωm ÷ 99.9 Ωm / 0.1 Ωm/Calculated value, consider earth resistance 4-wire method
100 Ωm ÷ 999 Ωm / 1 Ωm/ Calculated value, consider earth resistance 4-wire method
1.00 kΩm ÷ 9.99 kΩm / 0.01 kΩm/ Calculated value, consider earth resistance 4-wire method
10.0 kΩm ÷ 99.9 kΩm / 0.1 kΩm/ Calculated value, consider earth resistance 4-wire method
100 kΩm / 1 kΩm / Calculated value, consider earth resistance 4-wire method
TRMS CLAMP CURRENT
(Measuring range/ Resolution/ Accuracy)
0.0 mA ÷ 99.9 mA / 0.1 mA / ±(3 % of reading + 3 digits)
100 mA ÷ 999 mA / 1 mA / ±(3 % of reading + 3 digits)
1.00 A ÷ 19.99 A / 0.01 A / ±(3 % of reading + 3 digits)
GENERAL DATA
Power supply voltage: 6 x 1.5 V battery or rechargeable battery, size AA
Operation time: Typical 20 h
Overvoltage category: 50 V CAT IV
Protection classification: Double insulation
Protection degree: IP 40
Display: 128 x 64 dots matrix display with backlight
Memory: 1900 measurements
Connectivity: RS232 and USB
Weight: 0.85 kg (without battery cells)
Dimensions (W x H x D): 14 cm x 8 cm x 23 cm
인증된 전문가에게 직접 연결