Drop: 7.2 Vdc
Height: 20.2 mm
Offset: 50% of selected max. value
Weight: 50 g
Accuracy: ± 0.05 %
Diameter: 44 mm
RTD Type: Ni100,Pt100
Approvals: "Authority Requirements: EMC: 2014/30/EU RoHS: 2011/65/EU EAC: TR-CU 020/2011"
Isolation: 1500 V
Stability: ≤ 0.01% of span/100 Ω (Load Stability)
Vibration: IEC 60068-2-6;2 to 25 Hz: ±1.6 mm;25 to 100 Hz: ±4 g
Input Type: Thermocouple, RTD, Resistance, Voltage
Calibration: TXUN-KIT Communication Tool Kit
Output Load: ≤ (Vsupply - 7.2)/0.023 Ω
Sensor Type: Transmitter
EMC Standard: NAMUR NE 21
Probe Length: 0 mm
Warm Up Time: 5 min
Accuracy Note: ≤ ±0.05% of span
Output Detail: Min. Signal Range: 16 mA NAMUR NE43 Upscale/Downscale: 23 mA/3.5 mA
Response Time: 1 to 60 sec
ADC Resolution: 20 bit
DAC Resolution: 16 bit
Humidity Range: Up to 95% non-condensing
Sensor Current: 0.2 mA
Supply Voltage: 7.2 to 35 Vdc
Sheath Material: N/A
Cable Resistance: 5 Ω
Input Resistance: 10 MΩ
Update Rate, Max: 440 ms
Electrical Output: 4 to 20 mA
Enclosure Ratings: IP00, IP68
Power Dissipation: 25 mW to 0.8 W
Supply Power Type: DC
Thermocouple Type: B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Signal/Noise Ratio: > 60 dB
Input Control Signal: -12 to 800 mV
Supply Power Effects: < 0.005% of span/Vdc
Electrical Connection: Screw Terminal
Programmable Functions: Loop Link and HART
Sensor Break Detection: 3.5 to 23 mA
Wiring/Connector Table: 2-, 3-, or 4-Wire
Temperature Coefficient: ≤ ±0.01%/°C
Temperature Input Range: N/A
Cold Junction Compensation: < ±1.0°C
Operating Temperature, Max: 85 °C
Operating Temperature, Min: -40 °C
Calibration Temperature, Max: 28 °C
Calibration Temperature, Min: 20 °C