For full functionality of this site it is necessary to enable JavaScript.
EMIN.VN
0
Product image

Senseca TG50-3-2R-00-00-5-00 온도 조절 장치 (24 V DC, ± 15 %)

ModelTG50-3-2R-00-00-5-00
문의하기
안전한 결제
품질 보장
간편 교환 및 반품
배송 가능

No alarm output A3,A4

Power supply

Supply voltage : 24 V DC, ± 15 %

                         : < 5 VA

Operating temperature : -10..+55 °C

CE-conformity : EN 61326-1:2013; EN 60664-1:2007

Input

Fault function : break of wire (RTD Pt100/1000, Thermocouple) and short-circuit (only Pt100/1000)

RTD : Pt100 (3-wire) -100.0..+600.0 °C

      Pt1000 (3-wire) -100.0..+300.0 °C

    : Thermocouple (TC)

      type J -100.0..+800.0 °C

      type K -150..+1200 °C

      type N -150..+1200 °C

      type S -50..+1600 °C

cold junction compensation integrated

Accuracy : <0.1 %, ±1 Digit

Display : Graphic LCD-Display, 128 x 64 Pixel, with white back-lite

Output

Alarm A1-A4 : relay SPDT 

              < 250 V AC < 250 VA < 2 A

              cos Phi ≥ 0.3

              < 300 V DC < 40 W <2 A

- Accuracy : 0.2 %;TK 0.01 %/K

Fault indication : for broken line or short circuit detection

→ analog output (programmable)

0 mA, < 3.6 mA or >21.5 mA

→ Alarm relays

min. or max. function programmable

Case : Polyamide (PA) 6.6 , UL94V-0

TS35 acc. to DIN EN 60715:2001-09

Weight : approx. 450 g

Connection : screw terminals 0.14..2.5 mm²

                     AWG 26..AWG14

Protection class : case IP30, terminals IP20 acc. to BGV A3

Datasheet


Manual


혜택 소식 받아보기

대량 할인, 도매 가격 업데이트 및 신제품 소식을 이메일로 받아보세요.

구독하면 당사의 서비스 이용약관개인정보 처리방침에 동의하는 것으로 간주됩니다.

빠른 지원

인증된 전문가에게 직접 연결