- in high-voltage circuit breaker contacts,
- in disconnecting switches, separators, and short-circuiters,
- in packaged switchgears,
- in contact couplings,
- in weld seams, etc.
인증된 전문가에게 직접 연결
인증된 전문가에게 직접 연결

One of the problems faced when measuring the transient resistances with permissible error is availability of oxide films between contact surfaces.
According to International standard IEC 60694 "General Specifications for High-Voltage Switch Gears" (International Electrotechnical Commission), for controlling this type of error, amperage of the test current during testing the electric resistance in the main circuit of a HV circuit breaker shall be between 50A and its rated value.
Current amperage in the passport data of many foreign circuit breakers is most often limited by specific values: 100A and 200A.
Amperage in the MIKO-21 can be set in several ways:
Only SKB EP microohmmeters measure transient resistances (R transient) of minimum-oil and bulk-oil circuit breakers using separate automatic modes optimized for those circuit breakers. Current transformers (CT) of bulk-oil circuit breakers form a prolonged transition process when the test current is applied. For this reason the time of measurement is determined by CT parameters, by their number, amperage and, for example, for U-220-2000-25U1 circuit breaker it may be as high as 30 seconds. Special algorithms with automatic stop of measurements allow avoidance of subjective mistakes and increase the number of measurements per one battery charge.
There are four methods programmed in the instrument for resistance measurement start-up:
Company archive of passport values of resistances (R transient) of circuit breaker contacts ensures automatic comparison between measured and passport values subject to circuit breaker grade indication;
Archive of the instrument contains passports of HV circuit breakers with indication of maximum and/or minimum permissible transient resistances of contacts, and passports for rejected resistors with indication of permissible values of the upper and lower thresholds of resistances.
The user can also add the required template.
Availability of an in-built archive of passport values of eclectic resistances (main circuit of HV circuit breakers) facilitates automatic detection, and the device beeps if the results of measurements go beyond the permissible limits.
Color graphic display of high brightness ensures easy reading on a sunny day, whereas intuitively understandable interface with a sensor display facilitates the instrument use.
The Instrument can be manipulated either from the film keyboard or from the sensor display, as suits.
Communication with PC via USB or a flash card facilitates data transfer from the Instrument to the Company data base.
The instrument can be built-in into testing systems under control of software complexes of diagnosis laboratories and equipment manufacturers.
For convenience the standard kit includes only one type of a test package (Kit 3 includes two test cables with crocodile clips for high-voltage circuit breakers up to 110 kV).
Suitable cable or a set of cables can be selected from a large range of additional accessories:
One set with spring-loaded contacts for measurements in busbars or in arc extinguish chambers. Two other kits with crocodile clips (with current and potential wires) for circuit breakers of up to 10 kV, circuit breakers of up to 110 kV, and a part for circuit breakers of up to 220kV.
Three kits that include cables with crocodile clips (with current and potential wires), a cable with a G-clamp (with current and potential wires). They differ in length and purpose, namely: for HV circuit breakers of up to 220kV, for HV circuit breakers of up to 330kV, some for 500kV, and for HV circuit breakers of up to 750kV.
|
Specifications |
Value |
|
Range of resistance measurements, Ohm |
0.1 µΩ ÷ 2 Ω |
|
Range of test current amperage, A |
1 ÷ 200 |
|
Error of measurements, % |
±0.05 |
|
Time of measurement in Mode 1, sec |
not more than 2.0 |
|
Time of measurement in Mode 2 on a bulk-oil circuit breaker, sec |
10 ÷ 30 |
|
Time of measurement in Mode 3 on a bulk-oil circuit breaker with battery charge saving |
5 ÷ 15 |
|
Period of continuous operation (in normal conditions), hrs, no less than |
8 |
|
Number of tests (in normal conditions), no less than |
500 |
|
Display of the instrument |
Sensor, color, graphic, 480x272 dots |
|
Types of data transfer channels |
USB/USB Flash |
|
Consumed power does not exceed, V |
60 |
|
Operating temperature range, ºС |
-20 ÷ +50 |
|
Weight of the test block, kg, not more than |
3.1 |
|
Dimensions, mm |
270х250х130 |
|
Interface language |
English |
|
User manuals language |
English |
|
Calibration period, year |
3 |
| Photo | Item, Index | Application |
|---|---|---|
|
USB 2.0 A-B Cable | For computer connection and data transfer. |