直接联系认证专家
Function
Channels: 4–20mA: 8/16/24/32 is optional; RS485 – up to 64 channels
Suitable detector: detectors with 4–20mA or AE-RS485
Electric
Power supply: 220 VAC
Power consumption: ≤ 8 W
Signal input: RS485 / 4–20 mA
Signal output: RS485
Wiring: 4–20 mA: three-wire; RS485: four-wire
Suitable cable: RVVP 3×1.5 / 4×1.0 mm²
Relay output: 3 passive relays (250 VAC / 5 A 30 VDC / 5 A)
Display & Operation
Display: LCD
Indicator light:
AGS1000; AGS1000D – alarm, fault, power, self-test
AGS1000B – power, backup power, alarm, fault, block
Operation method: button
Environment
Operating temperature: 0 °C ~ 40 °C
Operating humidity: 10 ~ 95 % RH (non-condensing)
Operating pressure: 80 ~ 120 kPa
Structure
Body material: carbon steel with electrostatic spraying
Weight:
AGS1000 – about 7.5 kg
AGS1000B – about 16.5 kg
AGS1000D – about 50 kg
Dimensions (H×W×D):
AGS1000 – 500 × 360 × 100 mm
AGS1000B – 590 × 400 × 155 mm
AGS1000D – 700 × 620 × 244 mm
Certificate
SIL: SIL2
EX: Ex db II BT6 Gb