For full functionality of this site it is necessary to enable JavaScript.
EMIN.VN
0
Product image

FLUKE FLUKE-381 钳形表 (AC 999.9A/2500A ; True RMS)

ModelFLUKE-381
P/N3610452
原产地China
不含增值税
19,584,902 VND
含增值税
21,151,694 VND
安全结算
品质保证
轻松更换与退货
支持配送

Remote Display: Wireless (30 ft)

ACA (jaw): 999.9A /0.1A /2% ± 5 digits

ACA (iFlex): 2500A /0.1A /3% ± 5 digits

DCA: 999.9A /0.1A /2% ± 5 digits

ACV: 1000V /0.1V /1.5% ± 5 digits

DCV: 1000V /0.1V /1% ± 5 digits

R: 60,000 Ω /0.1 Ω /1% ± 5 digits

F: 500 Hz /0.1 Hz /0.5% ± 5 digits

True-RMS: Yes

Continuity: Yes

Hold: Yes

Backlight: Yes

Min/Max/Avg: Yes

Inrush: Yes

Wire capacity:750 MCM or 2-500 MCM

Diameter conductor: 1.3" or 34 mm max

Size: 10.905 x 3.464 x 1.629 in (277 x 88 x 43 mm)

Weight: 12 oz. (350g)

Included: 18-inch iFlex™ flexible current probe, Coated instruction card, Safety information sheet, Soft carrying case, TL75 test leads,Five AA Alkaline batteries


Features and benefits

  • Wireless technology allows the display to be carried up to 30 ft. away from the point of measurement for added flexibility without interference with measurement accuracy
  • The removable magnetic display can be conveniently mounted where it is easily seen
  • iFlex flexible current probe expands the measurement range to 2500 A ac
  • CAT IV 600 V, CAT III 1000 V
  • Integrated low pass filter and state of the art signal processing allows for use in noisy electrical environments while providing stable readings
  • Proprietary inrush measurement technology to filter out noise and capture motor starting current exactly as the circuit protection sees it
  • Ergonomic design fits in your hand and can be used while wearing protective equipment
  • Radio transmitter automatically sets the correct measurement range so you do not need to change the switch positions while taking a measurement
  • Three-year warranty
  • Soft carrying case

Safety conformance
IEC/EN 61010-1:2001, 1000V CAT III, 600V CAT IV

What’s the difference between the clamp meter models?

  Fluke-365 Fluke-373 Fluke-374 Fluke-375 Fluke-376 Fluke-381
Measure ac current 200.0 A 600.0 A 600.0 A 600.0 A 999.9 A 999.9 A
Measure ac current via iFlex     2500 A 2500 A 2500 A 2500 A
Measure ac voltage 600.0 V 600.0 V 600.0 V 600.0 V 1000.0 V 1000.0 V
Measure continuity ≤ 30 Ω ≤ 30 Ω ≤ 30 Ω ≤ 30 Ω ≤ 30 Ω ≤ 30 Ω
Measure dc current 200.0 A   600.0 A 600.0 A 999.9 A 999.9 A
Measure dc voltage 600.0 V   600.0 V 600.0 V 1000.0 V 1000.0 V
Measure resistance 6,000 Ω 6,000 Ω 6,000 Ω 60k Ω 60k Ω 60k Ω
Measure frequency       500 Hz 500 Hz 500 Hz
Measure inrush     100 mS 100 mS 100 mS 100 mS
Work in poorly lit areas Backlight Backlight Backlight Backlight Backlight Backlight
Measure non-linear loads True-rms True-rms True-rms True-rms True-rms True-rms
 

381 Data Sheet »