Giải pháp giám sát khí rò rỉ chống cháy nổ cho nhà xưởng

2026年11月20日 15時11分51秒

Đối với đội ngũ kỹ sư cơ điện (M&E), bộ phận an toàn môi trường (HSE) và chủ đầu tư nhà máy, việc nắm rõ các yêu cầu mới không chỉ giúp hoàn thiện hồ sơ pháp lý mà còn định hình lại tiêu chuẩn lựa chọn hệ thống máy đo khí lắp cố định tại các khu vực có nguy cơ cháy nổ cao.

From the second half of 2025 into 2026, the legal framework on fire prevention, firefighting, and rescue (PCCC & CNCH) in Vietnam has undergone major adjustments to strengthen early warning capabilities and risk control across production facilities. At the core of this regulatory update is Decree 105/2025/ND-CP guiding the implementation of the Law on Fire Prevention, Firefighting, and Rescue, alongside supplementary regulations issued in 2026 such as Decree 69/2026/ND-CP, Decree 347/2026/ND-CP, Circular 62/2026/TT-BCA, and National Technical Regulation QCVN 10:2025/BCA.

For mechanical and electrical (M&E) engineers, health, safety, and environment (HSE) teams, and plant owners, understanding these requirements not only supports regulatory compliance but also reshapes selection criteria for fixed gas detectors in high-risk hazardous areas.

Key Technical Priorities for 2025–2026:

Facilities under fire safety management (chemical warehouses, gas filling stations, basements, solvent workshops) must tighten early leak detection, prove explosion-proof ratings (ATEX/IECEx) in hazardous zones, and ensure reliable interlock signals (4-20mA / RS485) to control panels.

1. Core Changes in 2025–2026 Fire Safety Regulations Impacting Gas Monitoring Infrastructure

The updated regulatory system clearly defines the self-inspection and fire safety maintenance responsibilities of facility heads while standardizing technical requirements for equipment installed on site. Under QCVN 10:2025/BCA and its guiding decrees, facilities subject to fire safety oversight—particularly chemical storage areas, gas filling stations, generator rooms, technical basements, and lines handling volatile solvents—must ensure early hazard detection during vapor or gas accumulation before sparks or open flames occur.

In addition, fire equipment management mechanisms have shifted toward stricter conformity verification from circulation through commissioning. Rather than relying on subjective checks, authorities require equipment installed in explosive atmospheres (Zone 1, Zone 2) to demonstrate explosion-proof protection (ATEX or IECEx), resistance to harsh environments, and seamless integration with ventilation systems, emergency shut-off valves, or fire alarm control panels. Delayed deployment or selecting the wrong sensing principle for the target gas can directly prevent operational safety acceptance.

2. Engineering Challenges When Integrating Fixed Gas Detectors into Plant Safety Systems

Unlike portable instruments used for periodic spot checks, fixed gas monitoring systems run continuously 24/7 as the first line of defense in a fire safety interlock chain. In practice, however, many plant installations underperform because engineers select an unsuitable sensing technology or signal interface.

For combustible gases such as Methane (CH4), LPG, Hydrogen (H2), or organic solvent vapors, measurements must accurately reflect percentage of lower explosive limit (%LEL). In areas with high solvent vapor concentrations or environments prone to poisoning catalytic surfaces (such as silicones, sulfur compounds, or lead), non-dispersive infrared (NDIR) sensors deliver far greater stability and service life than conventional catalytic bead sensors. Conversely, for confined spaces or wastewater treatment stations generating toxic gases like H2S, CO, NH3, or oxygen (O2) depletion, selective electrochemical sensors are essential to minimize false alarms.

Target Gas GroupOptimal Sensor TechnologyStandard Safety Interlock Action
Combustible Gases (CH4, LPG, H2) Catalytic Bead Level 1 (10–20% LEL): Exhaust fan & audible/visual alarm.
Level 2 (25–50% LEL): Emergency gas shut-off valve.
Solvent Vapors / Sensor-Poisoning Environments Non-Dispersive Infrared (NDIR) 4-20mA / RS485 output to PLC to trigger forced ventilation and zone power cut-off.
Toxic Gases & Oxygen (CO, H2S, NH3, O2) Electrochemical Local evacuation warning and automatic fresh air supply for confined spaces.

Regarding control architecture, field transmitters should provide standardized industrial outputs such as 4-20mA analog or RS485 Modbus RTU digital communication to central controllers or building PLCs. When gas concentration reaches the first alarm threshold, the controller activates local alarms and boosts exhaust airflow; if concentration escalates to the second threshold, relay contacts immediately close solenoid shut-off valves or de-energize electrical circuits to eliminate ignition sources.

3. Selecting Fixed Gas Detector Configurations for Real-World Plant Operation

To meet strict explosion-proof standards under current regulations while integrating smoothly into existing plant infrastructure, facilities should prioritize industrial gas transmitters with proven field reliability.

Solutions for Chemical Warehouses & Gas Filling Stations (Zone 1 / Zone 2)

Explosion-proof cast aluminum transmitters such as Prosense P-Series suited for demanding zones thanks to Ex d IIC T6 explosion-proof enclosures and IP65/IP66 protection against dust and water jets. They support catalytic, infrared, and electrochemical sensor options with clear local displays for straightforward reading and on-site calibration.

Solutions for Electronics Lines, Laboratories & Industrial Gas Stations

For production lines requiring high sensitivity and multi-point coordination, Cosmos KD-12B fixed gas detectors  paired with a central control unit provide long-term operational stability with minimal zero drift. Standardized 4-20mA outputs allow M&E engineers to wire directly into SCADA or fire safety interlock panels without complex signal converters.

4. Commissioning and Maintenance Considerations Under Updated Rules

Selecting the right hardware solves only half of the safety equation. To keep systems operational in line with periodic inspection and maintenance expectations under 2026 fire safety regulations, plant engineering teams should establish quarterly bump tests with calibration gas and full calibrations every 6–12 months. Calibration certificates, interlock relay test logs, and explosion-proof documentation should be kept organized for routine fire safety inspections. You can review full implementation details in our guide on leak gas monitoring solutions for factory fire prevention. 

Explore combustible gas, toxic gas, and control unit options at EMIN Vietnam.

相关新闻

Storing insulin at the wrong temperature: the medication becomes ineffective, yet it’s impossible to tell by looking at it
2026年11月19日 10時00分13秒

When insulin and other biological products are stored outside the recommended temperature range (2°C to 8°C for unopened products), their protein structures become denatured, leading to a reduction or complete loss of therapeutic activity. In many cases, the medication may be compromised without showing any visible signs, posing a risk of difficult-to-control hyperglycemia and constituting a violation of pharmaceutical storage standards