Gossen Metrawatt SMARTCONTROL LON Multifunctional Data Logger (24 V DC; LON interface module)

ModelSMARTCONTROL LON
P/NU300E
联系我们
安全结算
品质保证
轻松更换与退货
支持配送

System Data

Memory capacity: 2 MB flash ring buffer

Memory expansion:Internal card slot for microSD card, optional 4 GB microSD card, formatting via the SMARTCONTROL manager

Storage rules: Cyclical or based on conditions

Calculations: Mean value generation, heating and cooling quantities, timer programs, limit value monitoring, calculator, integral value generation

Programming: Each channel separately, graphic programming using function blocks with the SMARTCONTROL manager

Time Battery-backed real-time clock

System monitoring: Watchdog timer

Control keys: F1, reset on the system PCB

SMARTCONTROL Standard

Housing material: Steel sheet metal

Dimensions: 226 x 210 x 70 mm

Mounting: Screw mounted

Protection: IP 20

Weight: 1.5 kg

Mains power:

SMARTCONTROL can be operated with 12 ... 24 V DC.

Power consumption*:

– Basic PCB < 2.5 W

– Expansion for LON interface module: additionally max. 1 W

– Expansion for input/output module for 24 channels: additionally max. 10 W

Input: 100 ... 240 V AC, 50 ... 60 Hz

Output: 12 V DC

Option: External power pack (primary switched mode) Z301U

Operating conditions: 5 ... 50 °C, no condensation

Real Time Clock Battery

Lithium cell (replaceable without the use of tools and data loss): CR 2032 3 V; for the preservation of time and date

Permanent operation: Replacement every 5 years

Non-operating time/ lengthy storage periods: Replacement every 2 years